Parameter
Address Name / seng range / [default seng] Informaon
0x2838:003
(P203.03)
Start/stop conguraon: Stop method
(St
art/stop confg: Stop method)
Response aer stop command.
0 Coasng The motor has no torque (coasts down to standsll).
1 Standard ramp The motor is brought to a standsll with deceleraon me 1 (or
deceleraon me 2, if acvated).
•
Deceleraon me 1 can be set in 0x2918 (P221.00).
•
Deceleraon me 2 can be set in 0x291A (P223.00).
4Ramp mes^ 66
2 Quick stop ramp The motor is brought to a standsll with the deceleraon me set for
the "Quick s
top" funcon.
•
Deceleraon me for quick stop can be set in 0x291C (P225.00).
•
The "quick stop" funcon can also be acvated manually, for instance
via a digital input. 4Flexible I/O conguraon of the start, stop and
rotang
direcon commands^ 48
3 Switch-o posioning (from version 05.01) Is similar to the stop method "Standard ramp [1]". Depending on the
current output frequency, however, the inverter delays the beginning of
the down-ramping so that the number of motor revoluons unl a
standsll and thus the stopping posion is always relavely constant.
4
"Switch-o posioning" stop mode ^ 126
Basic seng
Stop behavior
37