10.2 Congure analog inputs
10.2.1
Analog input 1
Sengs for analog input 1.
Intended use
The analog input 1 can be used for the following tasks:
As a standard setpoint source
Intended use Parameter Seng Further
informaon
As a setpoint source for specifying
a frequency setpoint.
0x2860:001
(P201.01)
Analog input 1
[2]
Frequency control 4St
andard setpoint source ^ 65
As setpoint source for dening the
r
eference value for the process
controller.
0x2860:002
(P201.02)
Analog input 1
[2]
Frequency control 4
Conguring the process controller ^ 98
As a setpoint source for dening a
t
orque setpoint.
0x2860:003
(P201.03)
Analog input 1
[2]
Torque control4St
andard setpoint source ^ 131
As an
alternave to the seng as a standard setpoint source, the "Acvate AI1 setpoint" 0x2631:014 (P400.14) funcon can be used to enable a
setpoint change-over to the analog input 1.
As an actual v
alue source or speed feedforward source for the process controller:
Intended use Parameter Seng Further
informaon
As an actual value source for the
process controller.
0x4020:002
(P600.02)
Analog input 1
[1]
Frequency control 4
Conguring the process controller ^ 98
As a speed feedforward source for
the pr
ocess controller.
0x4020:004
(P600.04)
Analog input 1
[2]
Details
The following sengs are possible for the analog input:
Denion of the input range
Filt
er me for low-pass lters
Monit
oring of the input signal
Dead band for eliminang the smallest signal levels
Denion of the seng range
AI1
0x2636:0020x2636:0080x2636:001
%
Hz
0x2636:006
0x2636:0030x2636:009
0x2636:010
0x2636:007
0x2636:004
0x2636:005
%
PID
X3
%
V/mA
0x2DA4:002
0x2DA4:003
x y
<
>
0x2860:001
0x2860:002
[Hz]
[PID unit]
0x2636:011
0x2636:012
%
%
0x2DA4:004
0x2860:003
[%]
unit
Analog input 1 [2]
Torque setpoint source
Analog input 1 [2]
Process controller setpoint source
Frequency setpoint source
Analog input 1 [2]
Diagnosc parameters:
The fr
equency value is displayed in 0x2DA4:002 (P110.02).
The process controller value is displayed in 0x2DA4:003 (P110.03).
The torque value is displayed in 0x2DA4:004 (P110.04).
Denion of the input range
The analog input can be congured as voltage or current input. Internally, the signal is always
converted to a value in percent.
Denion of the seng range
The seng range results from the set min and max value for the respecve mode.
I/O extensions and control connecons
Congure analog inputs
Analog input 1
205