Example of allocang priority
Parameter Designaon Seng for this example
0x2631:014 (P400.14) Acvate AI1 setpoint Digital input 5 [15]
0x2631:016 (P400.16) Acvate keypad setpoint Digital input 4 [14]
Digital input 4 Digital input 5 Acve setpoint source
FALSE FALSE Standard setpoint source set in 0x2860:001
(P201.01)
FALSE TRUE Analog input 1
TRUE FALSE Keypad
TRUE TRUE Keypad (since "Digital input 4" trigger is higher in the selecon list than "Digital input 5" trigger)
Parameter
Address Name / seng range / [default seng] Informaon
0x2631:014
(P400.14)
Funcon list: Acvate AI1 setpoint
(Funcon list: Setp: AI1)
•
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the
"Acvate AI1 setpoint" funcon.
Trigger = TRUE: analog input 1 is used as setpoint source (if the trigger
assigned has the highest setpoint priority).
Trigger = FALSE: no acon / deacvate funcon again.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:015
(P400.15)
Funcon list: Acvate AI2 setpoint
(Funcon list: Setp: AI2)
•
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the
"Acvate AI2 setpoint" funcon.
Trigger = TRUE: analog input 2 is used as setpoint source (if the trigger
assigned has the highest setpoint priority).
Trigger = FALSE: no acon / deacvate funcon again.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:016
(P400.16)
Funcon list: Acvate keypad setpoint
(Funcon list: Setp: Keypad)
•
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the
"Acvate keypad setpoint" funcon.
Trigger = TRUE: the keypad is used as setpoint source (if the trigger
assigned has the highest setpoint priority).
Trigger = FALSE: no acon / deacvate funcon again.
Notes:
•
The default keypad setpoint can be changed in keypad operang
mode via the arrow keys of the keypad.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:018
(P400.18)
Funcon list: Acvate preset (bit 0)
(Funcon list: Setp: Preset b0)
•
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the
"Acvate preset (bit 0)" funcon.
The bit with the valency 2
0
for bit-coded selecon and the acvaon of a
parameterised setpoint (preset).
Trigger = FALSE: bit = "0".
Trigger = TRUE: bit = "1".
14 Digital input 4 State of X3/DI4, taking an inversion set in 0x2632:004
(P411.04) into
consideraon.
0x2631:019
(P400.19)
Funcon list: Acvate preset (bit 1)
(Funcon list: Setp: Preset b1)
•
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the
"Acvate preset (bit 1)" funcon.
The bit with the valency 2
1
for bit-coded selecon and the acvaon of a
parameterised setpoint (preset).
Trigger = FALSE: bit = "0".
Trigger = TRUE: bit = "1".
15 Digital input 5 State of X3/DI5, taking an inversion set in 0x2632:005 (P411.05) into
consideraon.
0x2631:020
(P400.20)
Funcon list: Acvate preset (bit 2)
(Funcon list: Setp: Preset b2)
•
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the
"Acvate preset (bit 2)" funcon.
The bit with the valency 2
2
for bit-coded selecon and the acvaon of a
parameterised setpoint (preset).
Trigger = FALSE: bit = "0".
Trigger = TRUE: bit = "1".
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:021
(P400.21)
Funcon list: Acvate preset (bit 3)
(Funcon list: Setp: Preset b3)
•
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the
"Acvate preset (bit 3)" funcon.
Selecon bit with the valency 2
3
for the bit-coded selecon and
acvaon of a parameterised setpoint (preset value).
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
0 Not connected No trigger assigned (trigger is constantly FALSE).
Conguring the frequency control
Changing the se
tpoint source during operaon
112