10.2.2 Analog input 2
Sengs for analog input 2.
Intended use
The analog input 2 can be used for the following tasks:
As a s
tandard setpoint source
Intended use Parameter Seng Further
informaon
As a setpoint source for specifying
a frequency setpoint.
0x2860:001
(P201.01)
Analog input 1
[3]
Frequency control 4St
andard setpoint source ^ 65
As setpoint source for dening the
r
eference value for the process
controller.
0x2860:002
(P201.02)
Analog input 1
[3]
Frequency control 4
Conguring the process controller ^ 98
As a setpoint source for dening a
t
orque setpoint.
0x2860:003
(P201.03)
Analog input 1
[3]
Torque control4St
andard setpoint source ^ 131
As an
alternave to the seng as a standard setpoint source, the "Acvate AI2 setpoint" 0x2631:015 (P400.15) funcon can be used to enable a
setpoint change-over to the analog input 2.
As an actual v
alue source or speed feedforward source for the process controller:
Intended use Parameter Seng Further
informaon
As an actual value source for the
process controller.
0x4020:002
(P600.02)
Analog input 2
[2]
Frequency control 4
Conguring the process controller ^ 98
As a speed feedforward source for
the pr
ocess controller.
0x4020:004
(P600.04)
Analog input 2
[3]
Details
The following sengs are possible for the analog input:
Denion of the input range
Filt
er me for low-pass lters
Monit
oring of the input signal
Dead band for eliminang the smallest signal levels
Denion of the seng range
AI2
0x2637:0020x2637:0080x2637:001
%
Hz
0x2637:006
0x2637:0030x2637:009
0x2637:010
0x2637:007
0x2637:004
0x2637:005
X3
%
V/mA
0x2DA5:002
0x2DA5:003
x y
<
>
0x2860:001
0x2860:002
[Hz]
[PID unit]
0x2637:011
0x2637:012
%
%
0x2DA5:004
0x2860:003
[%]
%
PID
unit
Analog input 2 [3]
Torque setpoint source
Analog input 2 [3]
Process controller setpoint source
Frequency setpoint source
Analog input 2 [3]
Diagnosc parameters:
The fr
equency value is displayed in 0x2DA5:002 (P111.02).
The process controller value is displayed in 0x2DA5:003 (P111.03).
The torque value is displayed in 0x2DA5:004 (P111.04).
For further details and conguraon examples, see chapter "Analog input 1". ^ 205
Parameter
Address Name / seng range / [default seng] Informaon
0x2637:001
(P431.01)
Analog input 2: Input range
(Analog input 2: AI2 input r
ange)
Denion of the input range.
0 0 ... 10 VDC
1 0 ... 5 VDC
2 2 ... 10 VDC
I/O extensions and control connecons
Congure analog inputs
Analog input 2
209