6.3 Control/restrict direcon of rotaon of the motor
In the default seng, both direcons of motor rotaon are enabled. Oponally, the direcon
of rotaon can be restricted so that only a clockwise rotaon (CW) of the motor is possible.
Precondions
Wiring of the motor phases must be carried out correctly with regard to the direcon of
mot
or rotaon.
In the documentaon and the parameter selecon texts, the following terms are used for the
direcon of rotaon:
F
orward = clockwise direcon of rotaon (CW)
R
everse = counter-clockwise direcon of rotaon (CCW)
Details
The direcon of rotaon of the motor can be controlled in various ways:
Via the funcon "Reverse rotaonal direcon". Possible triggers for the funcon "Reverse
rotaonal direcon" are available for selecon in 0x2631:013 (P400.13), e.g.the digital
inputs and internal status signals of the inverter.
Via the network. The denion of the direcon of rotaon is possible via the mappable
NetWordIN1 data word or oneof the predened process data words.
By specifying a bipolar setpoint value via an analog input. Either via a bipolar input range
(-10 ... +10 V) or the conguraon of a bipolar seng range.
If a reversal of rotaon is not required, the direcon of rotaon can be restricted in 0x283A
(P304.00) to "Only clockwise (CW) [0]".
Parameter
Address Name / seng range / [default seng] Informaon
0x283A
(P304.00)
Limitaon of rotaon
(Limit. rotaon)
Oponal
restricon of the rotang direcon.
0 Only clockwise (CW) The motor can only be rotated clockwise (CW). The transfer of negave
frequency and PID setpoints to the motor control is prevented.
This funcon takes eect aer the "Reverse rotaonal direcon"
funcon (0x2631:013 (P400.13)).
Since this funcon only prevents negave setpoints, counter-
clockwise rotaon (CCW) is possible if the motor has been wired for
this rotang direcon.
1 Both rotaonal direcons Both direcons of motor rotaon are enabled.
Related topics
4Ex
ample: Start/stop (1 signal) and reversal ^ 54
Start, stop and rotang
direcon commands
Control/restrict direcon of rotaon of the motor