14.5.1.1 Timeout for error response
If an error occurs that does not immediately cause a switch-o, the "Fault reacon acve"
device status inially becomes acve. The motor is brought to a standsll with quick stop
r
amp. The change to the device status "Fault" is only made aer the quick stop (motor at
standsll) has been executed or aer an adjustable meout me has expired.
Details
In the device status "Fault reacon acve"
only the par
ameters of the inverter can be changed that do not require an inverter disable.
a holding brake in brake mode 0x2820:001 (P712.01) = "Automacally (via device state)
[0]" is trig
gered for closing.
the motor control connues to be operable.
1
2
0
Mains on
Quick stop active
Switch-on
disabled
Trouble
Fault reaction
active
Operation
enabled
Switched on
Not ready
to switch on
Ready
to switch on
From all states
Power secon inhibited (pulse inhibit)
Power secon enabled
Diagnosc parameters:
0x282A:005
(P126.05) displays the current device status of the inverter
Parameter
Address Name / seng range / [default seng] Informaon
0x2826 Time-out for error response
0.0 ... [6.0] ... 100.0
s
This mer is started when a change-over to the "Fault reacon acve"
device status takes place. If the motor is sll rotang aer the me-out
me has elapsed, a change-over to the "Fault" device status takes place.
In case of a serious error, an immediate change-over to the "Fault"
device status takes place.
CAUTION!
Changing this par
ameter may cause a longer rampme in the event of an
error. This must be considered when changing this parameter.
Related topics
4
Automac restart aer a fault^ 226
Diagnoscs and fault eliminaon