Address Name / seng range / [default seng] Informaon
0x282A:004 Status words: Extended status word
R
ead only
Bit-coded status word.
Bit 8 Reverse rotaonal direcon 1 = reversal acve.
Bit 10 Inverter disabled (safety) Not available.
Bit 11 STO acve
0x282A:005
(P126.05)
Status words: Device status
(Status words: Device status)
Read only
Display of the current inverter device state.
0 Inialisaon
2 Not ready to switch on
3 Switch on disabled
4 Ready to switch on
5 Switched on
6 Operaon enabled
7 Disable operaon
8 Shut down
9 Quick stop acve
10 Fault reacon acve
11 Fault
0x282B:001
(P125.01)
Inverter diagnoscs: Acve control source
(Inverter diag.: Acve control)
Read only
Display of the control source that is currently acve.
0 Flexible I/O conguraon
1 Network
2 Keypad
8 Keypad full control
9 Manual mode
0x282B:002
(P125.02)
Inverter diagnoscs:
Acve setpoint source
(Inverter diag.: Acve setpoint)
Read only
Display of the setpoint source that is currently acve.
0 Not selected
1 Analog input 1
2 Analog input 2
3 Keypad Setpoint
4 HTL input
5 Network Setpoint
9 Manual mode: setpoint
11 Setpoint preset 1
12 Setpoint preset 2
13 Setpoint preset 3
14 Setpoint preset 4
15 Setpoint preset 5
16 Setpoint preset 6
17 Setpoint preset 7
18 Setpoint preset 8
19 Setpoint preset 9
20 Setpoint preset 10
21 Setpoint preset 11
22 Setpoint preset 12
23 Setpoint preset 13
24 Setpoint preset 14
25 Setpoint preset 15
50 Motor potenometer
51 PID setpoint (fr
om version 04.00)
Diagnoscs and fault eliminaon
Diagnosc parameters
In
verter diagnoscs