Address Name / seng range / [default seng] Informaon
0x282B:003
(P125.03)
Inverter diagnoscs: Keypad LCD status
(In
verter diag.: Keypad LCD stat.)
•
Read only
Bit-coded state of the keypad status displays.
Bit 0 LOC 1 = local keypad control acve.
Bit 1 REM 1 = remote control via terminals, network, etc. acve.
Bit 2 MAN 1 = manual setpoint selecon via keypad acve.
Bit 3 Auto 1 = automac setpoint selecon via terminals, network, etc. acve.
Bit 4 Set 1 = a parameter seng has been changed but not been saved yet in the
memory module with mains failure protecon .
0x282B:004
(P125.04)
Inverter diagnoscs: Acve drive mode
(Inverter diag.: Drive mode)
•
Read only
Display of the acve drive mode.
0 Velocity mode "Velocity mode" acve.
1 PID control PID control acve.
2 Torque mode (from version 03.00) "Torque mode" acve.
4 Jog operaon "Jog foward (CW)" or "Jog reverse (CCW)" funcon acve.
0x2831 Inverter-Statuswort
•
Read only
Bit coded status word of the internal motor control.
Bit 1 Speed setpoint 1 limited 1 = input of speed controller 1 in limitaon.
Bit 2 Speed controller in limitaon 1 = output of speed controller 1 in limitaon.
Bit 3 Torque setpoint limited 1 = setpoint torque in limitaon.
Bit 4 Soll-Q-Strom limiert 1 = setpoint current in limitaon.
Bit 5 Speed setpoint 2 limited 1 = input of speed controller 2 in "torque mode" in limitaon.
Bit 6 Obere Drehzahlgrenze akv 1 = in "torque mode", the speed is limited to upper speed limit
0x2946:001
(P340.01) .
Bit 7 Untere Drehzahlgrenze akv 1 = in "torque mode", the speed is limited to lower speed limit
0x2946:002 (P340.02) .
Bit 8 Flying restart acve -
Bit 10 Output frequency limited 1 = setpoint frequency with V/f operaon in limitaon.
Bit 11 Magnesaon completed 1 = during V/f operaon, the factor 7 rotor me constant has passed
(calculated from the me at which the inverter was enabled without
restart on the y and with a total motor current of 20 % rated motor
current for the rst me). Otherwise 0.
Bit 12 Motorphasenfehler 1 = motor phase failure detecon acve.
Bit 14 Error reset blocking me acve 1 = the error can only be reset when the blocking me has elapsed.
0x2833 Inverter status word 2
•
Read only
Bit-coded status word 2 of the inverter.
Bit 1 Manual test mode acve 1 = manual test mode acve.
Bit 2 Manual control acve 1 = manual control acve.
Bit 6 DC braking acve 1 = DC braking
acve.
Bit 15 UPS operaon acve 1 = UPS operaon acve.
Funcon is not supported in this device.
0x293A
(P116.00)
Actual switching frequency
(Actual sw. freq.)
•
Read only
Display of the currently acve switching frequency of the inverter.
Example:
•
"16 kHz variable / drive-opmised / 4 kHz min. [22]" is selected as
switching frequency in 0x2939 (P305.00).
•
An increase of the ambient temperature and/or the load have caused
a decrease of the switching frequency to 8 kHz. In this case, this
parameter indicates the selecon "8 kHz power loss-opmized [7]".
1 2 kHz drive-opmized
2 4 kHz drive-opmized
3 8 kHz drive-opmized
4 16 kHz drive-opmized
5 2 kHz power loss-opmized
6 4 kHz power loss-opmized
7 8 kHz power loss-opmized
8 16 kHz power loss-opmized
Diagnoscs and fault eliminaon
Diagnosc parameters
In
verter diagnoscs
277