EasyManua.ls Logo

Lenze i410 - Example: Change-Over from Terminal Control to Keypad Control

Lenze i410
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.4.1 Example: Change-over from terminal control to keypad control
The c
ontrol is executed primarily via the I/O terminals: Switch S1 serves to start and stop
the motor.
Switch S2 serves to oponally change over to local keypad control. In case of acvated
keypad control, the motor can only be started via the
keypad key. However, the
condion is that switch S1 is closed.
If s
witch S1 is opened again or the
keypad key is pressed, the motor is stopped
(irrespecve of the acve control source).
F
or details of the keypad control of the inverter, see the chapter "Keypad operang mode".
^ 245
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Switch S2 Acvate keypad control
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:012 (P400.12) Acvate keypad control Digital input 2 [12]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
Start, stop and rotang
direcon commands
Changing the control source during operaon
Example: Change-over from terminal control to keypad control
62

Table of Contents

Other manuals for Lenze i410

Related product manuals