Notes:
•
In c
ase of an acvated keypad or network control, the "Run" 0x2631:002 (P400.02)
funcon must be set to TRUE to start the motor in addion to the inverter enable. Either
via digital input or by the "Constant TRUE [1]" seng.
•
In c
ase of an acvated keypad or network control, the following funcons are sll acve:
•
0x2631:001 (P400.01): Enable inverter
•
0x2631:002 (P400.02): Run
•
0x2631:003 (P400.03): Acvate quick stop
•
0x2631:004
(P400.04): Reset fault
•
0x2631:005 (P400.05): Acvate DC braking
•
0x2631:010 (P400.10): Jog foward (CW)
•
0x2631:011 (P400.11): Jog reverse (CCW)
•
0x2631:012 (P400.12): Acvate keypad control
•
In case of an acvated network control, the following addional funcons are sll acve:
•
0x2631:013
(P400.13): Reverse rotaonal direcon
•
The
funcons for setpoint change-over.4Changing the setpoint source during
operaon ^ 111
All other funcons congurable via 0x2631:xx (P400.xx) are deacvated in case of keypad
or network control.
Diagnosc parameters:
•
0x282A:001 (P126.01): Cause of disable
•
0x282A:002 (P126.02): Cause of quick stop
•
0x282A:003 (P126.03): Cause of stop
•
0x282B:001 (P125.01): Acve control source
Start, stop and rotang
direcon commands
Changing the control source during operaon
61