0x282A:001
(P126.01)
Status words: Cause of disable
(St
atus words: Cause of disable)
Read only
Bit-coded display of the cause(s) for disabled inverter.
Bit 0 Flexible I/O conguraon 1 = the inverter was disabled by the trigger set in 0x2631:001 (P400.01).
Bit 1 Network 1 = the inverter was disabled via network.
Bit 2 Axis command 1 = the inverter was disabled via axis command .
Bit 6 Fault DC-bus 1 = The inverter was disabled due to a DC-bus error.
Bit 7 Drive not ready 1 = the inverter was disabled internally since the drive was not ready for
operaon.
Possible causes:
Under/overvoltage in the DC bus
Defecve device hardware
Bit 8 Quick stop acve 1 = the inverter was disabled by the "Quick stop" funcon.
Bit 9 Motor data idencaon 1 = the inverter was disabled by the "Automac idencaon of the
motor data" funcon.
Bit 10 Holding brake 1 = the inverter was disabled by the "Holding brake control" funcon.
Bit 11 DC braking -
Bit 12 CiA402 Inverter disabled 1 = the inverter was disabled by the internal state machine.
The bit is only set if
Operang mode 0x6060 (P301.00) = "CiA: Velocity mode [2]" and
state machine in the "Switch on disabled" state and
the state change has not been carried out via the "Disable operaon"
command.
Bit 13 CiA402 Quick stop opon code 2 1 = the inverter was disabled by the "Quick stop" funcon.
Bit 14 Safety Funcon is not supported in this device.
Bit 15 CiA402 operaon mode 0 1 = the inverter has been disabled because the selecon "No mode
change/no mode assigned [0]" is set in 0x6060 (P301.00).
0x282A:002
(P126.02)
Status words: Cause of quick stop
(Status words: Cause of QSP)
Read only
Bit coded display of the cause(s) of quick stop.
Bit 0 Flexible I/O conguraon 1 = quick stop was acvated by the trigger set in 0x2631:003
(P400.03).
Bit 1 Network 1 = quick stop was acvated via network.
Bit 2 Axis command 1 = quick stop was acvated via axis command .
Bit 6 Error response 1 = quick stop has been acvated as a response to an error.
0x282A:003
(P126.03)
Status words: Cause of stop
(Status words: Cause of stop)
Read only
Bit coded display of the cause(s) of stop.
Bit 0 Flexible I/O: Start disabled 1 = stop was acvated by the trigger set in 0x2631:002 (P400.02).
Bit 1 Flexible I/O: Run forward 1 = stop has been acvated due to cancellaon of the command "Run
forward (CW)".
Bit 2 Flexible I/O: Run reverse 1 = stop has been acvated due to cancellaon of the command "Run
reverse (CCW)".
Bit 3 Flexible I/O: Jog forward 1 = stop has been acvated due to cancellaon of the command "Jog
f
oward (CW)".
Bit 4 Flexible I/O: Jog reverse 1 = stop has been acvated due to cancellaon of the command "Jog
reverse (CCW)".
Bit 5 Network 1 = stop was acvated via network.
Bit 6 Keypad 1 = stop was acvated via keypad.
Bit 7 Control mode transion 1 = stop has been acvated due to a change of the operang mode.
Bit 8 End of sequence 1 = stop was acvated by the "sequencer" funcon since the sequence is
completed.
The bit is only set aer the sequence is completed if End of sequence
mode0x402F (P824.00) is set ="Stop [1]" or "Stop and abort [2]".
Bit 9 Manual mode -
Bit 15 Waing for start 1 = stop is acve as a start command is not yet available (e. g. aer
enabling the inverter).
Diagnoscs and fault eliminaon
Diagnosc parameters
In
verter diagnoscs
275