6 Start, stop and rotang
direcon commands
6.1 Control selecon
The selected "control source" serves to provide the inverter with its start, stop, and reversal
commands.
Possible control sources:
Digital inputs
Keypad
1
0
0x2631:012
1
0
0x2824
0x2838:001
0x2838:003
0x2631:008
0x2631:009
0
1
1
0
CTRL
Keypad full control active
Connection list
Run
0x2631:002
0x282B:001
Active control source
0: flexible I/O configuration
1: keypad
8: keypad full control
Run
Stop
Stop ("KSTOP")
0: flexible I/O configuration
1: keypad
Control selection
Motor control
Stop method
Start method
Start/Stop
Keypad
Run forward (CW)
Activate keypad control
Run reverse (CCW)
Flexible I/O configuration
NOTICE
Stop commands are always acve from any connected source, regardless of which control
sour
ce is selected!
If, for example, the network control is acvated and a keypad is plugged in for diagnosc
purposes, the motor is also stopped when the
keypad key is pressed.
Excepon: a stop command has no eect in jog operaon.
Details
The de
fault seng "Flexible I/O conguraon [0]" in 0x2824
(P200.00) enables a exible
control of the inverter via digital inputs, network and keypad. The control of the inverter
via the digital inputs is precongured. For details see the subchapter "Flexible I/O
conguraon". ^ 45
If the keypad is to be used as the control source for the applicaon, set "Keypad [1]" in
0x2824 (P200.00). For details, see subchapter "Keypad control". ^ 46
The control source that is currently acve is displayed in 0x282B:001 (P125.01).
Start, stop and rotang direcon commands
43