80 % / 40 Hz
100 % / 50 Hz
60 Hz
80 % 80 %
20 Hz
0x2DDD
Run
Running [50]
Stop active [53]
Digital input 1 [11]
Constant TRUE [1]
Digital input 2 [12]
Frequency setpoint selection
PID feedback = setpoint [73]
Output signals
Status signals
Output frequency
Deactivate PID controlling
Enable inverter
Input signals
Process setpoint
FunctionTrigger
The status signals can be assigned to digital outputs. 4
Congure digital outputs ^ 211
①
PID control is deacvated: a change-over is iniated from the congured PID control to speed-controlled operaon.
②
PID control is acvated again: a change-over is iniated from speed-controlled operaon back to the congured PID control.
7.3.5 Process controller diagnoscs
The following parameters serve to diagnose the process controller.
Parameter
Address Name / seng range / [default seng] Informaon
0x401F:001
(P121.01)
Current setpoint
(PID se
tpoint)
•
Read only: x.xx PID unit
Display of the current reference value (setpoint) for the process
controller.
0x401F:002
(P121.02)
Current process variable
(PID process var.)
•
Read only: x.xx PID unit
Display of the current controlled feedback variable (actual value) for the
process controller.
0x401F:003
(P121.03)
Status
(PID status)
•
Read only
Bit-coded status display of the process controller.
Bit 0 Process controller o
Bit 1 PID output set to 0
Bit 2 PID I-component inhibited
Bit 3 PID inuence acve
Bit 4 Setpoint = actual value
Bit 5 Sleep mode acve
Bit 6 Max. alarm
Bit 7 Min. alarm
0x401F:004 PID control value
•
Read only: x.x Hz
•
From version 03.00
Display of the output frequency aer the PID controller, but without any
inuencing factor.
Conguring the frequency control
Conguring the process controller
Pr
ocess controller funcon selecon
109