14 Diagnoscs and fault eliminaon
This secon contains informaon on error handling, drive diagnoscs and fault analysis.
14.1 LED status display
The "RDY" and "ERR" LED status displays on the front of the inverter provide some quick
informaon about certain operang states.
"RDY" LED (blue) "ERR" LED (red) Status/meaning
O O No supply voltage.
on on
Inializaon (inverter is started.)
Blinking (2 Hz)
O Inverter inhibited.
Blinking fast (4 Hz)
Inverter disabled, warning acve.
4Err
or handling ^ 284
on
Inverter disabled, error acve.
4Err
or handling ^ 284
Lights up briey once
e
very 1.5 s
Inverter inhibited, no DC-bus voltage.
on for a short me
every 1 s
USB module is connected, 5-V supply voltage for the USB module is available.
on
O
Inverter enabled.
The mot
or rotates according to the specied setpoint or quick stop acve.
Blinking fast (4 Hz)
Inverter enabled, warning acve.
The motor rotates according to the specied setpoint or quick stop acve.
Blinking (1 Hz)
Inverter enabled, quick stop as response to fault acve.
4Error handling ^ 284
Both LEDs are blinking in a rapidly alternang
mode
Firmware update acve.
4Upda
te device rmware ^ 227
Both LEDs are blinking in a very rapidly
s
ynchronous mode
"Visual tracking" funcon is
acve.
4
Opcal device idencaon ^ 219
Diagnoscs and fault eliminaon
LED status display
268