Parameter
Address Name / seng range / [default seng] Informaon
0x2838:001
(P203.01)
Start/stop conguraon: Start method
(St
art/stop confg: Start method)
Seng can only be changed if the inverter is
disabled.
Response aer starng command.
0 Normal Aer start command, the standard ramps are acve.
Acceleraon me 1 can be set in 0x2917 (P220.00).
Deceleraon me 1 can be set in 0x2918 (P221.00).
1 DC braking Aer start command, the "DC braking" funcon is
acve for the me set
in 0x2B84:002 (P704.02).
4DC braking^ 158
CAUTION!
Deacvate
automac DC braking, if a holding brake is used.
2 Flying restart circuit Aer the start command, the ying restart circuit is acve.
The ying restart funcon makes it possible to restart a coasng motor
during operaon without speed feedback. The course between the
inverter and motor is coordinated so that the transion to the rotang
motor is eected without jerk at the me of connecon.
4Flying r
estart circuit^ 154
3 Pre-magnesaon (from version 05.03) This seng corresponds to the seng [0] Normal, but adds the
premagnesaon of the motor before the rotaon/acceleraon begins.
The premagnesaon can reduce the motor current during the
acceleraon and generate a more even acceleraon curve (by avoiding
overcurrent situaons).
The premagnesaon funcon is relevant when operang in V/f motor
control modes. The premagnesaon causes a slight delay before the
motor acceleraon begins (typically 50-200 ms, depending on motor
characterisc).
0x2838:002
(P203.02)
Start/stop conguraon: Start at power-up
(Start/stop confg: Start at powerup)
Start behavior aer switching on the mains voltage.
0 O No automac start aer switching on mains voltage. In addion to the
inverter enable, a renewed start command is always required to start the
motor.
1 On Automac start of the motor aer switching on the mains voltage if the
inverter is enabled and a start command exists.
Related topics
4St
art, stop and rotang direcon commands ^ 43
Basic seng
Start behavior
35