EasyManua.ls Logo

Lenze i410 - Page 51

Lenze i410
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Address Name / seng range / [default seng] Informaon
70 Frequency threshold exceeded TRUE if current output frequency > frequency threshold. Otherwise
F
ALSE.
Display of the current output frequency in 0x2DDD (P100.00).
Seng Frequency threshold in 0x4005 (P412.00).
4Trigger acon if a frequency threshold is exceeded^ 242
71 Actual speed = 0
TRUE if current output frequency = 0 Hz (± 0.01 Hz),
irrespecve of the
operang mode. Otherwise FALSE.
Display of the current output frequency in 0x2DDD (P100.00).
78 Current limit reached
TRUE if current motor current ma
ximum current. Otherwise FALSE.
Display of the present motor current in 0x2D88 (P104.00).
Seng for the maximum current in 0x6073 (P324.00).
79 Torque limit reached (from version 02.00) TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
Seng "Actual posive torque limit" in 0x2949:003 (P337.03).
Seng Actual negave torque limit in 0x2949:004 (P337.04).
Motor torque monitoring ^ 197
81 Error of analog input 1 acve TRUE if the monitoring of the input signal at the analog input 1 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
Monit
oring threshold0x2636:008 (P430.08)
Monitoring condion0x2636:009 (P430.09)
The
seng of the Error response in 0x2636:010 (P430.10) has no eect
on this trigger.
4Analog input 1^ 205
82 Error of analog input 2 acve TRUE if the monitoring of the input signal at the analog input 2 has
r
esponded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
Monit
oring threshold0x2637:008 (P431.08)
Monitoring condion0x2637:009 (P431.09)
The
seng of the Error response in 0x2637:010 (P431.10) has no eect
on this trigger.
4Analog input 2^ 209
83 Load loss detected TRUE if actual motor current < threshold for load loss detecon
aer
delay me of the load loss detecon has elapsed. Otherwise FALSE.
Display of the present motor current in 0x6078 (P103.00).
Seng Threshold in 0x4006:001 (P710.01).
Seng Delay me in 0x4006:002 (P710.02).
4Load loss detecon^ 174
84 Heavy load monitoring TRUE if the actual apparent current of the motor exceeds the threshold
f
or longer than the delay me. FALSE if the actual apparent current of
the motor falls below the threshold value minus 5% (hysteresis) Heavy
load monitoring ^ 201 .
104 Local control acve TRUE if local keypad control ("LOC") acve. Otherwise FALSE.
105 Remote control acve TRUE if remote control ("REM") via terminals, network, etc. acve.
Otherwise FALSE.
106 Manual setpoint selecon acve TRUE if manual setpoint selecon ("MAN") via keypad acve. Otherwise
FALSE.
Selecon of the trigger for the "Acvate keypad setpoint" funcon in
0x2631:016 (P400.16).
107 Automac setpoint selecon acve TRUE if automac setpoint selecon ("AUTO") via terminals, network,
etc. acve. Otherwise FALSE.
Start, stop and rotang
direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
51

Table of Contents

Other manuals for Lenze i410

Related product manuals