59 Device trouble acve TRUE if a fault is acve. Otherwise FALSE.
In the e
vent of a fault, the motor is brought to a standsll with the
quick stop ramp. The inverter is then disabled.
Excepon: In case of a serious fault, the inverter is disabled
immediately. The motor has no torque (coasts).
The error state will be le automacally if the error condion is not
acve anymore.
The r
estart behaviour
aer trouble can be congured. 4Automac
restart aer a fault^ 226
60 Heatsink temperature warning acve TRUE if current heatsink temperature > warning threshold for
temperature monitoring. Otherwise FALSE.
Display of the current heatsink temperature in 0x2D84:001 (P117.01).
Seng of the warning threshold in 0x2D84:002.
68 Stop command acve TRUE if delay to standsll acve. Otherwise FALSE.
69 Rotaonal direcon reversed TRUE if output frequency is negave. Otherwise FALSE.
70 Frequency threshold exceeded TRUE if current output frequency > frequency threshold. Otherwise
FALSE.
Display of the current output frequency in 0x2DDD (P100.00).
Seng Frequency threshold in 0x4005 (P412.00).
4Trigger acon if a frequency threshold is exceeded^ 242
71 Actual speed = 0
TRUE if current output frequency = 0 Hz (± 0.01 Hz),
irrespecve of the
operang mode. Otherwise FALSE.
Display of the current output frequency in 0x2DDD (P100.00).
78 Current limit reached
TRUE if current motor current ma
ximum current. Otherwise FALSE.
Display of the present motor current in 0x2D88 (P104.00).
Seng for the maximum current in 0x6073 (P324.00).
79 Torque limit reached (from version 02.00) TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
Seng "Actual posive torque limit" in 0x2949:003 (P337.03).
Seng Actual negave torque limit in 0x2949:004 (P337.04).
Motor torque monitoring ^ 197
81 Error of analog input 1 acve TRUE if the monitoring of the input signal at the analog input 1 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
Monit
oring threshold0x2636:008 (P430.08)
Monitoring condion0x2636:009 (P430.09)
The
seng of the Error response in 0x2636:010 (P430.10) has no eect
on this trigger.
4Analog input 1^ 205
82 Error of analog input 2 acve TRUE if the monitoring of the input signal at the analog input 2 has
r
esponded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
Monit
oring threshold0x2637:008 (P431.08)
Monitoring condion0x2637:009 (P431.09)
The
seng of the Error response in 0x2637:010 (P431.10) has no eect
on this trigger.
4Analog input 2^ 209
83 Load loss detected TRUE if actual motor current < threshold for load loss detecon
aer
delay me of the load loss detecon has elapsed. Otherwise FALSE.
Display of the present motor current in 0x6078 (P103.00).
Seng Threshold in 0x4006:001 (P710.01).
Seng Delay me in 0x4006:002 (P710.02).
4Load loss detecon^ 174
84 Heavy load monitoring TRUE if the actual apparent current of the motor exceeds the threshold
f
or longer than the delay me. FALSE if the actual apparent current of
the motor falls below the threshold value minus 5% (hysteresis) Heavy
load monitoring ^ 201 .
104 Local control acve TRUE if local keypad control ("LOC") acve. Otherwise FALSE.
105 Remote control acve TRUE if remote control ("REM") via terminals, network, etc. acve.
Otherwise FALSE.
106 Manual setpoint selecon acve TRUE if manual setpoint selecon ("MAN") via keypad acve. Otherwise
FALSE.
Selecon of the trigger for the "Acvate keypad setpoint" funcon in
0x2631:016 (P400.16).
Start, stop and rotang
direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
Trigger list