59 Device trouble acve TRUE if a fault is acve. Otherwise FALSE.
•
In the e
vent of a fault, the motor is brought to a standsll with the
quick stop ramp. The inverter is then disabled.
•
Excepon: In case of a serious fault, the inverter is disabled
immediately. The motor has no torque (coasts).
•
The error state will be le automacally if the error condion is not
acve anymore.
•
The r
estart behaviour
aer trouble can be congured. 4Automac
restart aer a fault^ 226
60 Heatsink temperature warning acve TRUE if current heatsink temperature > warning threshold for
temperature monitoring. Otherwise FALSE.
•
Display of the current heatsink temperature in 0x2D84:001 (P117.01).
•
Seng of the warning threshold in 0x2D84:002.
68 Stop command acve TRUE if delay to standsll acve. Otherwise FALSE.
69 Rotaonal direcon reversed TRUE if output frequency is negave. Otherwise FALSE.
70 Frequency threshold exceeded TRUE if current output frequency > frequency threshold. Otherwise
FALSE.
•
Display of the current output frequency in 0x2DDD (P100.00).
•
Seng Frequency threshold in 0x4005 (P412.00).
4Trigger acon if a frequency threshold is exceeded^ 242
71 Actual speed = 0
TRUE if current output frequency = 0 Hz (± 0.01 Hz),
irrespecve of the
operang mode. Otherwise FALSE.
•
Display of the current output frequency in 0x2DDD (P100.00).
78 Current limit reached
TRUE if current motor current ≥ ma
ximum current. Otherwise FALSE.
•
Display of the present motor current in 0x2D88 (P104.00).
•
Seng for the maximum current in 0x6073 (P324.00).
79 Torque limit reached (from version 02.00) TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
•
Seng "Actual posive torque limit" in 0x2949:003 (P337.03).
•
Seng Actual negave torque limit in 0x2949:004 (P337.04).
Motor torque monitoring ^ 197
81 Error of analog input 1 acve TRUE if the monitoring of the input signal at the analog input 1 has
responded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
•
Monit
oring threshold0x2636:008 (P430.08)
•
Monitoring condion0x2636:009 (P430.09)
The
seng of the Error response in 0x2636:010 (P430.10) has no eect
on this trigger.
4Analog input 1^ 205
82 Error of analog input 2 acve TRUE if the monitoring of the input signal at the analog input 2 has
r
esponded. Otherwise FALSE.
This trigger is set as a funcon of the following sengs:
•
Monit
oring threshold0x2637:008 (P431.08)
•
Monitoring condion0x2637:009 (P431.09)
The
seng of the Error response in 0x2637:010 (P431.10) has no eect
on this trigger.
4Analog input 2^ 209
83 Load loss detected TRUE if actual motor current < threshold for load loss detecon
aer
delay me of the load loss detecon has elapsed. Otherwise FALSE.
•
Display of the present motor current in 0x6078 (P103.00).
•
Seng Threshold in 0x4006:001 (P710.01).
•
Seng Delay me in 0x4006:002 (P710.02).
4Load loss detecon^ 174
84 Heavy load monitoring TRUE if the actual apparent current of the motor exceeds the threshold
f
or longer than the delay me. FALSE if the actual apparent current of
the motor falls below the threshold value minus 5% (hysteresis) Heavy
load monitoring ^ 201 .
104 Local control acve TRUE if local keypad control ("LOC") acve. Otherwise FALSE.
105 Remote control acve TRUE if remote control ("REM") via terminals, network, etc. acve.
Otherwise FALSE.
106 Manual setpoint selecon acve TRUE if manual setpoint selecon ("MAN") via keypad acve. Otherwise
FALSE.
•
Selecon of the trigger for the "Acvate keypad setpoint" funcon in
0x2631:016 (P400.16).
Start, stop and rotang
direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
Trigger list