28833 0x70A1 Analog output 1 fault Keypad display: A
O1 fault
Cause Remedy Error type/response
Open circuit or short circuit at analog output 1.
Check wiring of analog output 1.
Check
denion of the output range in
0x2639:001 (P440.01).
Warning
Related topics
4Analog output 1 ^ 216
28834 0x70A2 Analog output 2 fault Keypad display: A
O2 fault
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
Open cir
cuit or short circuit at analog output 2.
Check wiring of analog output 2.
Check denion of the output range in .
Warning
28961 0x7121 Pole
posion idencaon fault Keypad display: Pole pos. error
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
Fault (congurable)
Seng parameters: 0x2C60
29056 0x7180 Motor overcurrent Keypad display: Mot ma
x current
Cause Remedy Error type/response
The motor current has exceeded the warning/
err
or threshold for the motor current
monitoring set in 0x2D46:001 (P353.01).
Check mot
or load.
Check drive dimensioning.
Check warning threshold or error threshold
set in 0x2D46:001 (P353.01).
Fault (congurable)
The error can only be reset aer a blocking
me.
Blocking me: 1 s
Seng parameters: 0x2D46:002
(P353.02)
Related topics
4Ov
ercurrent monitoring ^ 194
30336 0x7680 Memory module is full Keypad display: EPM full
Cause Remedy Error type/response
The memory module contains too many
par
ameter sengs.
Execute "Save user data" 0x2022:003 (P700.03)
device command again. This reinialises the
user memory with the current parameter
sengs. In this way, parameter sengs that are
no longer required are automacally deleted.
Warning
The parameter sengs were not saved in the
memory module.
30337 0x7681 Memory module not present Keypad display: EPM not pr
esent
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
Fault
30338 0x7682 Memory module: Invalid user data Keypad display: EPM in
valid data
Cause Remedy Error type/response
The user parameter sengs in the memory
module ar
e invalid.
1.
Ex
ecute user parameter sengs again.
2.
Ex
ecute device command "Save user data"
0x2022:003 (P700.03).
Fault
The user parameter sengs are lost.
The default sengs were automacally
loaded.
Diagnoscs and fault eliminaon
Error codes, causes and remedies