25505 0x63A1 CU: load error ID tag Keypad display: CU ID t
ag error
Cause Remedy Error type/response
Calibraon data of the control unit not
compable or faulty.
Upda
te
rmware of the inverter to the most
recent version.
If the error persists, the control unit or the
device has to be replaced. In this case, please
contact the manufacturer.
Fault
The inverter is disabled immediately. The
motor has no torque (coasts).
The error can only be reset by mains
switching.
25506 0x63A2 PU: load error ID tag Keypad display: PU ID t
ag error
Cause Remedy Error type/response
Calibraon data of the power unit not
compable or faulty.
Upda
te rmware of the inverter to the most
r
ecent version.
If the error persists, the power unit or the
device has to be replaced. In this case, please
contact the manufacturer.
Fault
The inverter is disabled immediately. The
motor has no torque (coasts).
The error can only be reset by mains
switching.
25507 0x63A3 Power unit unknown Keypad display: PU unkno
wn
Cause Remedy Error type/response
The power unit installed is not supported by the
soware.
Update
rmware of the inverter to the most
recent version.
Fault
The inverter is disabled immediately. The
motor has no torque (coasts).
The error can only be reset by mains
switching.
28800 0x7080 Asseron level monitoring (Low/High) Keypad display: Asseronlevel
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
The las
t seng of the connecon level diers
from the saved seng.
1.
Check seng in .
2.
Ex
ecute device command "Save user data"
0x2022:003 (P700.03).
3.
Switch inverter o and on again.
Fault
28801 0x7081 Analog input 1 fault Keypad display: AI1 f
ault
Cause Remedy Error type/response
The monitoring funcon of the input signal
congured for analog input 1 in 0x2636:008
(P430.08) and 0x2636:009
(P430.09) has been
triggered.
Check input signal a
t analog input 1.
Check conguraon of the monitoring
funcon.
Fault (congurable)
Seng parameters: 0x2636:010
(P430.10)
Related topics
4Analog input 1 ^ 205
28802 0x7082 Analog input 2 fault Keypad display: AI2 f
ault
Cause Remedy Error type/response
The monitoring funcon of the input signal
congured for analog input 2 in 0x2637:008
(P431.08) and 0x2637:009
(P431.09) has been
triggered.
Check input signal a
t analog input 2.
Check conguraon of the monitoring
funcon.
Fault (congurable)
Seng parameters: 0x2637:010
(P431.10)