Response
aer inial switch-on of the inverter
Aer switch-on, the inverter rst tries to load the parameter sengs stored in the user
memory. If the user memory is empty or damaged, an error message is output and the user
must intervene:
•
Case 1 = user memor
y empty: → default seng is loaded automacally from the rmware
→ data are saved automacally in the user memory of the memory module.
•
Case 2 = user memor
y damaged: → Error message → default seng is loaded
automacally → data are saved automacally in the user memory of the memory module.
•
Case 3 = OEM memory empty/damaged: → error message → data are loaded
automacally from the user memory of the memory module.
Parameter
Address Name / seng range / [default seng] Informaon
0x2022:003
(P700.03)
Device commands: Save user data
(De
vice commands: Save user data)
1 = save current parameter sengs in the user memory of the memory
module with mains failure protecon.
•
It ma
y take some seconds to execute the task. When the device
command has been executed successfully, the value 0 is shown.
•
Do not switch o the supply voltage during the saving process and do
not unplug the memor
y module from the inverter!
•
When the inverter is switched on, all parameters are automacally
loaded from the user memory of the memory module to the RAM
memory of the inverter.
0 O / ready Only status feedback
1 On / start Execute device command
2 In progress Only status feedback
3 Acon cancelled
4 No access
5 No access (Inverter disabled)
0x2022:004
(P700.04)
Device commands: Load user data
(Device commands: Load user data)
•
Seng can only be changed if the inverter is
disabled.
1 = load data from the user memory of the memory module to the RAM
memory of the inverter.
•
When the device command has been executed successfully, the value
0 is shown.
•
Loading parameters has a direct eect on the cyclic communicaon:
The data exchange for control is interrupted and a communicaon
error is generated.
0 O / ready Only status feedback
1 On / start Execute device command
2 In progress Only status feedback
3 Acon cancelled
4 No access
5 No access (Inverter disabled)
0x2022:005
(P700.05)
Device commands: Load OEM data
(De
vice commands: Load OEM data)
•
Seng can only be changed if the inverter is
disabled.
1 = load data from the OEM memory of the memory module to the RAM
memory of the inverter.
•
When the device command has been executed successfully, the value
0 is shown.
•
Loading parameters has a direct eect on the cyclic communicaon:
The data exchange for control is interrupted and a communicaon
error is generated.
0 O / ready Only status feedback
1 On / start Execute device command
2 In progress Only status feedback
3 Acon cancelled
4 No access
5 No access (Inverter disabled)
Device
funcons
Saving/loading the parameter sengs
222