Response
aer inial switch-on of the inverter
Aer switch-on, the inverter rst tries to load the parameter sengs stored in the user
memory. If the user memory is empty or damaged, an error message is output and the user
must intervene:
Case 1 = user memor
y empty: → default seng is loaded automacally from the rmware
→ data are saved automacally in the user memory of the memory module.
Case 2 = user memor
y damaged: → Error message → default seng is loaded
automacally → data are saved automacally in the user memory of the memory module.
Case 3 = OEM memory empty/damaged: → error message → data are loaded
automacally from the user memory of the memory module.
Parameter
Address Name / seng range / [default seng] Informaon
0x2022:003
(P700.03)
Device commands: Save user data
(De
vice commands: Save user data)
1 = save current parameter sengs in the user memory of the memory
module with mains failure protecon.
It ma
y take some seconds to execute the task. When the device
command has been executed successfully, the value 0 is shown.
Do not switch o the supply voltage during the saving process and do
not unplug the memor
y module from the inverter!
When the inverter is switched on, all parameters are automacally
loaded from the user memory of the memory module to the RAM
memory of the inverter.
0 O / ready Only status feedback
1 On / start Execute device command
2 In progress Only status feedback
3 Acon cancelled
4 No access
5 No access (Inverter disabled)
0x2022:004
(P700.04)
Device commands: Load user data
(Device commands: Load user data)
Seng can only be changed if the inverter is
disabled.
1 = load data from the user memory of the memory module to the RAM
memory of the inverter.
When the device command has been executed successfully, the value
0 is shown.
Loading parameters has a direct eect on the cyclic communicaon:
The data exchange for control is interrupted and a communicaon
error is generated.
0 O / ready Only status feedback
1 On / start Execute device command
2 In progress Only status feedback
3 Acon cancelled
4 No access
5 No access (Inverter disabled)
0x2022:005
(P700.05)
Device commands: Load OEM data
(De
vice commands: Load OEM data)
Seng can only be changed if the inverter is
disabled.
1 = load data from the OEM memory of the memory module to the RAM
memory of the inverter.
When the device command has been executed successfully, the value
0 is shown.
Loading parameters has a direct eect on the cyclic communicaon:
The data exchange for control is interrupted and a communicaon
error is generated.
0 O / ready Only status feedback
1 On / start Execute device command
2 In progress Only status feedback
3 Acon cancelled
4 No access
5 No access (Inverter disabled)
Device
funcons
Saving/loading the parameter sengs
222