30340 0x7684 Data not compl. saved before powerdown Keypad display: Sa
ve incomplete
Cause Remedy Error type/response
Saving of the parameter sengs was
in
terrupted by an unexpected disconnecon.
1.
Check user par
ameter sengs. (The loaded
back
up is an older version.)
2.
If required, repeat the changes made last.
3.
Execute device command "Save user data"
0x2022:003 (P700.03).
Warning
The user par
ameter sengs were not fully
saved.
At the next switch-on, the data stored are
copied to the user memory.
30342 0x7686 Internal communicaon error Keypad display: In
t. Comm.Err.
Cause Remedy Error type/response
Fault
30345 0x7689 Memory module: invalid OEM data Keypad display: OEM da
ta invalid
Cause Remedy Error type/response
The OEM memory contains invalid parameter
sengs or is empty.
Execute device command "Save OEM data"
0x2022:006 (P700.06).
Thus, the user parameter sengs get lost!
Warning
The user par
ameter sengs were
automacally loaded.
30346 0x768A Memory module: wrong type Keypad display: W
rong EPM
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
Fault
30352 0x7690 EPM
rmware version incompable Keypad display: EPM-FW incomp.
Cause Remedy Error type/response
The parameter sengs saved in the memory
module ar
e incompable with the rmware
version.
1.
Ex
ecute device command "Load default
sengs" 0x2022:001
(P700.01).
2.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
Fault
The data have been loaded into the RAM
memory, but they are incompable.
30353 0x7691 EPM data: rmware type
incompable Keypad display: EPM: FW incomp.
Cause Remedy Error type/response
The parameter sengs saved in the memory
module ar
e incompable with the rmware
type.
Example: Memory module of an inverter with
an applicaon IO is used in an inverter with a
standard IO.
1.
Ex
ecute device command "Load default
sengs" 0x2022:001
(P700.01).
2.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
Fault
The data have been loaded into the RAM
memory, but they are incompable.
30354 0x7692 EPM data: new rmware type detected Keypad display: UserCU not ma
tch
Cause Remedy Error type/response
The parameter sengs saved in the memory
module do not ma
tch the inverter hardware.
1.
Check par
ameter sengs.
2.
R
eset error.
3.
Execute "Save user data" 0x2022:003
(P700.03) or "Save OEM data" 0x2022:006
(P700.06) device command.
Fault
The da
ta have been loaded into the RAM
memory without being modied, and they
are compable.
The sengs loaded must be accepted by the
user (see remedy).