Address Name / seng range / [default seng] Informaon
0x2631:042
(P400.42)
Funcon list: Select parameter set (bit 1)
(Funcon list: Sel. paramset b1)
Seng can only be changed if the inverter is
disabled.
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the "Select parameter set (bit 1)" funcon.
Selecon bit with the valency 2
1
f
or "Parameter change-over" funcon.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x4046
(P755.00)
Acvaon of parameter set
(PSe
t acvaon)
Selecon of the acvaon method for the parameter change-over.
If the selecon is changed from "Via command... [0]/[1]" to "If the
selecon is changed...[2]/[3]" aer switch-on, the parameter set
selected via the funcons "Select parameter set (bit 0)" and "Select
parameter set (bit 1)" is acvated immediately. In case of selecon
[2], however, this only takes place if the inverter is disabled, the motor
is stopped or an error is acve.
0 Via command (disable required) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated if the trigger assigned
to the "Load parameter set" funcon in 0x2631:040 (P400.40) provides a
FALSE-TRUE edge AND the inverter is inhibited, the motor is stopped or
an error is acve.
4Ex
ample: Acvaon via command (only when disabled)^ 238
1 Via command (immediately) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is immediately acvated if the
trigger assigned to the "Load parameter set" funcon in 0x2631:040
(P400.40) provides a FALSE-TRUE edge.
4Example: Acvaon via command (immediately)^ 239
2 If the selecon is changed (disable required) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select par
ameter set (bit 1)" is acvated if the state of these
selecon bits changes AND the inverter is inhibited, the motor is
stopped or an error is acve.
4Ex
ample: Acvaon if the selecon is changed (only if the inverter is
disabled)^ 240
3 If the selecon is changed (immediately) The parameter set selected via the funcons "Select parameter set (bit
0)" and "Select parameter set (bit 1)" is acvated immediately if the
state of these selecon bits is changed.
4Example:
Acvaon if the selecon is changed (immediately)^ 241
Addional
funcons
Parameter change-over
Funcons for parameter change-over
237