65337 0xFF39 Motor overload Keypad display: Mot
or overload
Cause Remedy Error type/response
If the apparent motor current exceeds a dened
threshold value 0x4007:002 f
or a certain
amount of me 0x4007:001, heavy duty
monitoring is triggered.
Check the motor load. No response (congurable)
Seng parameters: 0x4007:003
65366 0xFF56 Maximum motor frequency reached Keypad display: Ma
x. motor freq.
Cause Remedy Error type/response
The
limitaon of the maximum motor speed
set in 0x6080 (P322.00) is acve.
The ma
ximum output frequency of the
inverter has been reached.
Depending on the parameter seng of
0x2D44:001
(P350.01) (Overspeed
monitoring: threshold), the speed limitaon
(0x6080 / Max. motor speed) may become
acve before speed monitoring.
Check applicaon. Warning
65393 0xFF71 Wrong password Keypad display: W
rong password
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
A wr
ong password has been entered several
mes.
Wait unl the blocking me has elapsed and
then enter the correct password.
Warning
The blocking me for entering a password is
more than 10 seconds. (The blocking me is
doubled every me an incorrect password is
entered.)
No password can be entered as long as the
blocking me is acve.
Related topics
65394 0xFF72 Warning Keypad display: W
arning
Cause Remedy Error type/response
Inverter is not
compable with the
Controller/PLC (brand protecon).
The Con
troller has not wrien a
deacvaon
password in the parameter yet.
The deacvaon password wrien by the
Controller is incorrect.
Use corresponding (compable) OEM
components.
Warning
No response from the inverter.
The decision on whether the machine will be
commissioned or not is made by the
Controller.
Related topics
65395 0xFF73 Fatal Error Keypad display: F
atal Error
Cause Remedy Error type/response
Error when reading the data from the control
unit.
S
witch inverter
o and on again.
If the error occurs again, the manufacturer
must be contacted, since the control unit or
the device has to be replaced.
Fault
Operaon of the inverter is not possible.
Diagnoscs and fault eliminaon
Error codes, causes and remedies