65337 0xFF39 Motor overload Keypad display: Mot
or overload
Cause Remedy Error type/response
If the apparent motor current exceeds a dened
threshold value 0x4007:002 f
or a certain
amount of me 0x4007:001, heavy duty
monitoring is triggered.
Check the motor load. No response (congurable)
Seng parameters: 0x4007:003
65366 0xFF56 Maximum motor frequency reached Keypad display: Ma
x. motor freq.
Cause Remedy Error type/response
•
The
limitaon of the maximum motor speed
set in 0x6080 (P322.00) is acve.
•
The ma
ximum output frequency of the
inverter has been reached.
•
Depending on the parameter seng of
0x2D44:001
(P350.01) (Overspeed
monitoring: threshold), the speed limitaon
(0x6080 / Max. motor speed) may become
acve before speed monitoring.
Check applicaon. Warning
65393 0xFF71 Wrong password Keypad display: W
rong password
Cause Remedy Error type/response
Error message is not available for the inverter
i410.
A wr
ong password has been entered several
mes.
Wait unl the blocking me has elapsed and
then enter the correct password.
Warning
•
The blocking me for entering a password is
more than 10 seconds. (The blocking me is
doubled every me an incorrect password is
entered.)
•
No password can be entered as long as the
blocking me is acve.
Related topics
65394 0xFF72 Warning Keypad display: W
arning
Cause Remedy Error type/response
Inverter is not
compable with the
Controller/PLC (brand protecon).
•
The Con
troller has not wrien a
deacvaon
password in the parameter yet.
•
The deacvaon password wrien by the
Controller is incorrect.
Use corresponding (compable) OEM
components.
Warning
•
No response from the inverter.
•
The decision on whether the machine will be
commissioned or not is made by the
Controller.
Related topics
65395 0xFF73 Fatal Error Keypad display: F
atal Error
Cause Remedy Error type/response
Error when reading the data from the control
unit.
•
S
witch inverter
o and on again.
•
If the error occurs again, the manufacturer
must be contacted, since the control unit or
the device has to be replaced.
Fault
•
Operaon of the inverter is not possible.
Diagnoscs and fault eliminaon
Error codes, causes and remedies
306