Address Name / seng range / [default seng] Informaon
0x4004:001
(P414.01)
MOP
starng values: Frequency
(MOP start value: Frequency)
0.0 ... [0.0] ... 599.0 Hz
Starng value for operang mode "MS: Velocity mode".
This value is used as inial value if "Starng value [1]" is set in 0x4003
(P413.00).
0x4004:002
(P414.02)
MOP starng values: PID value
(MOP start value: PID value)
-300.00 ... [0.00] ... 300.00 PID unit
Starng value for reference value of the PID control.
This value is used as inial value if "Starng value [1]" is set in 0x4003
(P413.00).
0x4004:003
(P414.03)
MOP starng values: Torque
(MOP s
tart value: Torque)
0.0 ... [0.0] ... 1000.0 %
Starng value for operang mode "MS: Torque mode".
This value is used as inial value if "Starng value [1]" is set in 0x4003
(P413.00).
100 % = motor rated torque (0x6076 (P325.00)).
0x4009:001 MOP values saved: Frequency
R
ead only: x.x Hz
Display of the last MOP value saved internally for the operang mode
"MS: Velocity mode".
This value is used as inial value if "Last value [0]" is set in 0x4003
(P413.00).
0x4009:002 MOP values saved: PID value
Read only: x.xx PID unit
Display of the last MOP value saved internally for the reference value of
the PID control.
This value is used as inial value if "Last value [0]" is set in 0x4003
(P413.00).
0x4009:003 MOP values saved: Torque
Read only: x.x %
Display of the last MOP value saved internally for the operang mode
"MS: Torque mode".
This value is used as inial value if "Last value [0]" is set in 0x4003
(P413.00).
100 % = motor rated torque (0x6076 (P325.00)).
0x4009:004 MOP values saved: Frequency setpoint
Read only: x.x Hz
0x4009:005 MOP values saved: PID setpoint
R
ead only: x.xx PID unit
A switch-over to the motor potenometer during operaon is also possible as an alternave
to the standard setpoint source seng.
4Ex
ample: Change-over from AI1 setpoint to MOP setpoint ^ 121
Conguring the frequency control
Congure setpoint sources
Mot
or potenometer (MOP)
72