Acc/Dec Time Setup via Multi-function Terminals – Setting Details
1–7
Set multi-step acceleration time1–7.
Set multi-step deceleration time1–7.
IN-65–71
Px Define (P1–P7)
Choose and configure the terminals to use for multi-step Acc/Dec time
inputs.
Acc/Dec commands are recognized as binary code inputs and will control the
acceleration and deceleration based on parameter values set with BAS-70–82
and BAS-71–83.
If, for example, the P6 and P7 terminals are set as XCEL-L and XCEL
respectively, the following operation will be available.
IN-89 In Check Time
Set the time for the inverter to check for other terminal block inputs. If IN-89 is
set to 100ms and a signal is supplied to the P6 terminal, the inverter searches
for other inputs over the next 100ms. When the time expires, the Acc/Dec
time will be set based on the input received at P6.