Table of Functions
171
6.4 Control Function group (PARCON)
In the following table, the data shaded in grey will be displayed when a related code has been
selected.
SL: Sensorless vector control (DRV-09) , I IM Sensorless, P PM Sensorless
*O/X: Write-enabled during operation
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F SL Ref.
00
-
Jump Code
Jump Code
1-99
4
O
O
I/P
p.52
04 0h1404
Carrier
frequency
Carrier Freq
Heavy
Duty
V/F:
1.0~15.0
(kHz)
23
IM:
2.0~15.0
(kHz)
PM:
2.0~10.0(kH
z)
3.0
X O I/P
-
Normal
Duty
24
V/F:
1.0~ 5.0
(kHz)
25
IM:
2.0~5.0
(kHz)
2.0 -
05 0h1405
Switching
mode
PWM
Mode
0
Normal
PWM
0:Norma
l PWM
X O I -
1
Lowleakage
PWM
09
26
0h1409
Initial
excitation
time
PreExTime 0.00-60.00(s) 1.00 X X I -
10
26
0h140A
Initial
excitation
amount
Flux Force 100.0-300.0(%) 100.0 X X I -
23
In case of 0.4~4.0kW, the setting range is 2.0~15.0(kHz)
24
PM synchronous motor sensorless vector control mode does not support normal duty
operation [when DRV-09 (Control Mode) is set to 6 (PM Sensorless)].
25
In case of 0.4~4.0kW, the setting range is 2.0~5.0(kHz).
26
Displayed when DRV-09 (Control Mode) is not set to 6 (PM Sensorless).