Code
Name LCD Display Setting Range
Property*
V/F SL Ref.
45
50
0h182D
proportional
PID P2-Gain 0.0-1000.0(%) 100.0 X O I/P -
6.9 Protection Function group (PAR→PRT)
In the following table, the data shaded in grey will be displayed when a related code has been
selected.
SL: Sensorless vector control (DRV-09) , I – IM Sensorless, P – PM Sensorless
*O/X: Write-enabled during operation,
Code
Name LCD Display Setting Range
Property*
V/F SL Ref.
00 - Jump Code Jump Code 1-99 40 O O I/P
p.52
04 0h1B04
Load level
setting
Load Duty
0 Normal Duty
1:Heavy
Duty
X O I/P
-
1 Heavy Duty
05 0h1B05
Input/output
open-phase
protection
Phase Loss
Chk
bit
00-11
00 X O
I/P
-
01
Output open
phase
10
Input open
phase
06 0h1B06
Input voltage
range during
open-phase
IPO V Band 1-100(V) 15 X O I/P
-
07 0h1B07
Deceleration
time at fault trip
Trip Dec
Time
0.0-600.0(s) 3.0 O O I/P
-
08 0h1B08
Selection of
startup on trip
reset
RST Restart
0 No
0:No O O I/P
-
1 Yes
09 0h1B09
Number of
automatic
restarts
Retry
Number
0-10 0 O O
I/P
-