198
Table of Functions
Code
Comm.
Address
Name LCD Display Setting Range
Initial
Value
Property*
V/F SL Ref.
10
51
0h1B0A
Automatic
restart
delay time
Retry Delay 0.0-60.0(s) 1.0 O O I/P
-
12 0h1B0C
Motion
at speed
command loss
Lost Cmd
Mode
0 None
0:None O O I/P
-
1 Free-Run
2 Dec
3 Hold Input
4 Hold Output
5 Lost Preset
13
52
0h1B0D
Time to decide
speed
command loss
Lost Cmd
Time
0.1-120(s)
1.0 O O I/P
-
14
52
0h1B0E
Operation
frequency
at speed
command
loss
Lost Preset F
Start frequency-
Maximum
frequency(Hz)
0.00 O O I/P
-
15
52
0h1B0F
Analog input
loss decision
level
AI Lost Level
0 Half x1
0:Half of
x1
O O I/P
-
1 Below x1
17 0h1B11
Overload
warning
selection
OL Warn
Select
0
No
0:No O O I/P
-
1 Yes
18 0h1B12
Overload alarm
level
OL Warn
Level
30-180(%)
150 O O
I/P
-
19 0h1B13
Overload
warning time
OL Warn
Time
0.0-30.0(s)
10.0 O O
I/P
-
20 0h1B14
Motion at
overload fault
OL Trip
Select
0
None
1:Free-
Run
O O
I/P
-
1
Free-Run
2 Dec
21 0h1B15
Overload fault
level
OL Trip Level 30-200(%)
180 O O
I/P
-
22 0h1B16
Overload fault
time
OL Trip Time 0.0-60.0(s)
60.0 O O
I/P
-
25 0h1B19
Underload
warning
selection
UL Warn Sel
0 No
0:No O O I/P
-
1 Yes
51
Displayed when PRT-09 is set higher than 0
52
Displayed when PRT-12 is not set to 0 (NONE)