RS-485 Communication Features
5.5.3 Inverter Memory Control Area Parameter (Read and Write)
Comm.
Address
Parameter Scale Unit
Changeable
During Operation
Function
0h03E0
Save parameters
-
-
X
0: No, 1:Yes
0h03E1
Monitor mode
initialization
- - O 0: No, 1:Yes
0h03E2
Parameter
initialization
- - X
0: No, 1: All Grp, 2: DRV Grp
3: BAS Grp, 4: ADV Grp, 5: CON
Grp
6: IN Grp, 7: OUT Grp, 8: COM
Grp
9: APP Grp, 12: PRT Grp, 13: M2
Grp
Setting is prohibited during
fault trip interruptions.
0h03E3
Display changed
parameters
- - O 0: No, 1: Yes
0h03E4
Reserved
-
-
-
-
0h03E5
Delete all fault
history
- - O 0: No, 1: Yes
0h03E6
Delete user-
registrated codes
- - O 0: No, 1: Yes
0h03E7
Hide parameter
mode
0 Hex O
Write: 0-9999
Read: 0: Unlock, 1: Lock
0h03E8
Lock parameter
mode
0 Hex O
Write: 0-9999
Read: 0: Unlock, 1: Lock
0h03E9
Easy start on
(easy parameter
setup mode)
- - O 0: No, 1: Yes
0h03EA
Initializing power
consumption
- - O 0: No, 1: Yes
0h03EB
Initialize inverter
operation
accumulative
time
- - O 0: No, 1: Yes
0h03EC
Initialize cooling
fan accumulated
operation time
- - O 0: No, 1: Yes