135
RS-485 Communication Features
Read Error Response
NAK
Station ID
CMD
Error code
SUM
EOT
15h
‘01’-FA
‘R’
‘**’
‘XX
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Total bytes=9
5.3.1.2 Detailed Write Protocol
Write Request: Writes successive n words to address XXXX.
ENQ Station ID CMD Address
Number of
Addresses
Data SUM EOT
05h
‘01’-FA
‘W’
‘XXXX
‘1’-8’ = n
‘XXXX
‘XX
04h
1 byte
2 bytes
1 byte
4 bytes
1 byte
n x 4 bytes
2 bytes
1 byte
Total bytes= (12 + n x 4): a maximum of 44
Write Normal Response
ACK
Station ID
CMD
Data
SUM
EOT
06h
‘01’-FA
‘W’
‘XXXX
‘XX
04h
1 byte
2 bytes
1 byte
n x 4 bytes
2 bytes
1 byte
Total bytes= (7 + n x 4): a maximum of 39
Write Error Response
NAK
Station ID
CMD
Error Code
SUM
EOT
15h
‘01’-FA
‘W’
‘**’
‘XX
04h
1 byte
2 bytes
1 byte
2 bytes
2 bytes
1 byte
Total bytes=9