186
Table of Functions
Code
Comm.
Address
Name
LCD
Display
Setting Range
Initial
Value
Property*
V/F SL Ref.
7
Iqse
8
Target Freq
9
Ramp Freq
10
Speed Fdb
12
PID Ref Value
13
PID Fdb Value
14
PID Output
15
Constant
08 0h1608
Analog output
2 gain
AO2 Gain -1000.0~1000.0(%) 100.0 O O I/P -
09 0h1609
Analog output
2 bias
AO2 Bias -100.0~100.0(%) 0.0 O O I/P -
10 0h160A
Analog output
2 filter
AO2 Filter 0~10000(ms) 5 O O I/P -
11 0h160B
Analog
constant
output 2
AO2
Const %
0.0~100.0(%) 0.0 O O I/P -
12 0h160C
Analog output
2 monitor
AO2
Monitor
0.0~1000.0(%) 0.0 O I/P -
30 0h161E
Fault output
item
Trip Out
Mode
bit
000-111
010 O O I/P -
1 Low voltage
2
Any faults other
than low
voltage
3
Automatic
restart final
failure
31 0h161F
Multi-function
relay 1 item
Relay 1
0
None
29:Trip O O I/P -
1
FDT-1
2
FDT-2
3
FDT-3
4
FDT-4
5
Over Load
6
IOL
7
Under Load
8
Fan Warning
9
Stall
10
Over Voltage
11
Low Voltage
12
Over Heat
13
Lost Command
14
Run
15
Stop

Table of Contents

Other manuals for LSIS S100