Technical Specification
Note
Precautions for 1phase input to 3-phase drive
Please connect single-phase input to R(L1) and T(L3).
AC or DC reactor is necessary to reduce DC ripple. Please select built-in reactor type for
30~75kW. For 0.4~22kW, external AC or DC reactor should be installed.
Same peripheral devices (including a fuse and reactor) as 3-phase can be used for 1-phase as
well.
If phase open trip occurs, please turn off the input phase open protection(PRT-05).
Protection for output current like OCT or IOLT is based on 3-phase input ratings which is
larger than single-phase input. User should set the parameters that are relative to motor
information(BAS-11~16), overload trip(PRT-17~22) and E-thermal functions(PRT-40~43)
Performance of sensorless control could be unstable depending on DC ripple.
The minimum input voltage must
be larger than 228Vac for 240Vac supply and 456Vac for 480Vac supply
to ensure motor voltage production of 207Vac and 415Vac, respectively.
To minimize the effect of voltage deprivation, please choose 208Vac motor for 240Vac supply
and 400Vac motor for 480Vac supply.