68
Learning Basic Features
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
DRV 07
Frequency reference
source
Freq Ref Src 2 V1 012 -
IN
01
Frequency at maximum
analog input
Freq at 100%
Maximum
frequency
0.00
Max.
Frequency
Hz
05 V1 input monitor
V1 Monitor
[V]
0.00 0.0012.00 V
06 V1 polarity options V1 Polarity 0 Unipolar
01
-
07
V1 input filter time
constant
V1 Filter 10 010000 ms
08
V1 minimum input
voltage
V1 volt x1 0.00 0.0010.00 V
09
V1 output at minimum
voltage (%)
V1 Perc y1 0.00 0.00100.00 %
10
V1 maximum input
voltage
V1 Volt x2 10.00 0 .0012.00 V
11
V1 output at maximum
voltage (%)
V1 Perc y2 100.00 0100 %
16
Rotation direction
options
V1 Inverting 0 No 0–1 -
17 V1 Quantizing level
V1
Quantizing
0.04
0.00*, 0.04
10.00
%
* Quantizing is disabled if 0’ is selected.

Table of Contents