363-206-305 Detailed Level Procedures:
Issue 3, June 2000 Page 1 of 2
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
DLP-540
Install HDSL Circuit Packs
1.
!
CAUTION:
In addition to primary lightning protection, an external Lightning and
Surge Secondary Protection Assembly (ED-8C783-30 or equivalent) is
required for
HDSL
circuits packs used in outside plant applications.
NOTE:
Take care to avoid damaging the LEDs that protrude through the opening
in the faceplate of the
HDSL
circuit pack.
NOTE:
To set switch to
ON
, depress rocker or slide switch toward side labeled
ON
in the figure. To set switch to
OFF
, depress rocker or slide switch
toward side labeled
OFF
in the figure.
Refer to Figure 1 and Table A and set option switches.
Table A – HDSL Control Switch Settings
Switch S1 Settings
Control Settings S1-1 S1-2 S1-3 S1-4
Master OFF OFF
Slave ON ON
Local OFF OFF
Remote ON ON