DLP-540
: Detailed Level Procedures 363-206-305
Page 2 of 2 Issue 3, June 2000
DDM-2000 F
IBER
R
EACH
W
IDEBAND
S
HELF
Figure 1 – HDSL Control Switch
2.
NOTE:
A maximum of three
BBF8 HDSL
circuit packs, including a protection
circuit pack, can be installed in one FiberReach if
28-Type
or
29-Type
OLIUs
are used.
Seat
BBF8
HDSL
circuit pack in required slot of
LOW SPEED
group being
equipped.
Response:
FAULT
LED on
HDSL
circuit pack lights and may remain lighted
for about 40 seconds and then goes off.
3. Repeat this procedure from
Step 1
for each service
HDSL
circuit pack being
installed.
4.
NOTE:
One protection
HDSL
circuit pack may be installed in slot
8(P)
of each
LOW SPEED
group being equipped.
If required, refer to Figure 1 and Table A, and set option switches on protection
HDSL
circuit pack.
5. If required, install protection
HDSL
circuit pack into slot
8(P)
of low-speed
group being equipped.
6. Install
177A
Retainer Cards into all unequipped service DS1
LOW SPEED
slots.
7.
STOP. YOU HAVE COMPLETED THIS PROCEDURE.