Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
MAIN: Trip cmd.block. USER
021 012
0: No Fig. 3-62, (p. 3-93)
[spacer]
Blocking the trip commands from the local control panel.
[spacer]
MAIN: Fct.assig.trip cmd.1
021 001
060 000: MAIN: Without function Fig. 3-62, (p. 3-93)
[spacer]
Assignment of signals that trigger trip command 1.
[spacer]
MAIN: Fct.assig.trip cmd.2
021 002
060 000: MAIN: Without function
[spacer]
Assignment of the signals that trigger trip command 2.
[spacer]
MAIN: Fct.assig.trip cmd.3
021 046
060 000: MAIN: Without function
[spacer]
Assignment of signals that trigger trip command 3.
[spacer]
MAIN: Fct.assig.trip cmd.4
021 047
060 000: MAIN: Without function
[spacer]
Assignment of signals that trigger trip command 4.
[spacer]
MAIN: Min.dur. trip cmd. 1
021 003
0.25 0.10 10.00 s Fig. 3-62, (p. 3-93)
Fig. 5-12, (p. 5-16)
[spacer]
Setting for the minimum duration of trip command 1.
[spacer]
MAIN: Min.dur. trip cmd. 2
021 004
0.25 0.10 10.00 s
[spacer]
Setting for the minimum duration of trip command 2.
[spacer]
MAIN: Min.dur. trip cmd. 3
021 032
0.25 0.10 10.00 s
[spacer]
Setting for the minimum duration of trip command 3.
[spacer]
MAIN: Min.dur. trip cmd. 4
021 033
0.25 0.10 10.00 s
[spacer]
Setting for the minimum duration of trip command 4.
[spacer]
MAIN: Latching trip cmd. 1
021 023
0: No Fig. 3-62, (p. 3-93)
[spacer]
Specification as to whether trip command 1 should latch.
[spacer]
MAIN: Latching trip cmd. 2
021 024
0: No
[spacer]
Specification as to whether trip command 2 should latch.
P634 7 Settings
7-80 P634/EN M/R-42-A // P634‑311‑653