Parameter Address
Default Min Max Unit Logic Diagram
Circuit breaker
failure protection
CBF_1: General enable USER
022 080
0: No Fig. 3-159, (p. 3-205)
[spacer]
CBF_2: General enable USER
022 214
0: No
[spacer]
CBF_3: General enable USER
022 228
0: No
[spacer]
CBF_4: General enable USER
022 242
0: No
[spacer]
Disabling or enabling circuit breaker failure protection.
[spacer]
CBF_1: Select. meas. input
022 156
0: End a
[spacer]
CBF_2: Select. meas. input
022 157
1: End b
[spacer]
CBF_3: Select. meas. input
022 158
2: End c
[spacer]
CBF_4: Select. meas. input
022 162
4: End d
[spacer]
Selection of measuring input – the circuit breaker failure protection is controlled
by its current.
[spacer]
CBF_1: Fct.assign. starting
022 202
060 000: MAIN: Without function Fig. 3-163, (p. 3-209)
[spacer]
CBF_2: Fct.assign. starting
022 216
060 000: MAIN: Without function
[spacer]
CBF_3: Fct.assign. starting
022 230
060 000: MAIN: Without function
[spacer]
CBF_4: Fct.assign. starting
022 244
060 000: MAIN: Without function
[spacer]
Select which of the trip commands is to be used as a start criterion for the CBF
function.
[spacer]
CBF_1: Start with man. trip
022 154
0: No Fig. 3-163, (p. 3-209)
[spacer]
CBF_2: Start with man. trip
022 175
0: No
[spacer]
CBF_3: Start with man. trip
022 176
0: No
P634 7 Settings
7-94 P634/EN M/R-42-A // P634‑311‑653