Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
CBF_4: Start with man. trip
022 177
0: No
[spacer]
Setting that permit a manual trip signal to also be used as a start criterion.
[spacer]
CBF_1: Fct.assignm. CBAux.
022 159
060 000: MAIN: Without function Fig. 3-163, (p. 3-209)
[spacer]
CBF_2: Fct.assignm. CBAux.
022 217
060 000: MAIN: Without function
[spacer]
CBF_3: Fct.assignm. CBAux.
022 231
060 000: MAIN: Without function
[spacer]
CBF_4: Fct.assignm. CBAux.
022 245
060 000: MAIN: Without function
[spacer]
Selection of trip signals – assigned to Gen. trip command 1 – for which, in
addition to current flow monitoring, status signals from CB auxiliary contacts are
evaluated.
[spacer]
CBF_1: I<
022 160
1.00 0.05 20.00 Inom Fig. 3-161, (p. 3-207)
Fig. 3-163, (p. 3-209)
Fig. 3-167, (p. 3-212)
Fig. 3-168, (p. 3-212)
[spacer]
CBF_2: I<
022 215
1.00 0.05 20.00 Inom
[spacer]
CBF_3: I<
022 229
1.00 0.05 20.00 Inom
[spacer]
CBF_4: I<
022 243
1.00 0.05 20.00 Inom
[spacer]
Setting for the threshold to detect a break in current flow.
[spacer]
CBF_1: IN<
022 180
1.00 0.05 20.00 Inom
[spacer]
CBF_2: IN<
022 181
1.00 0.05 20.00 Inom
[spacer]
CBF_3: IN<
022 182
1.00 0.05 20.00 Inom
[spacer]
CBF_4: IN<
022 183
1.00 0.05 20.00 Inom
[spacer]
Setting of the comparator threshold for residual current monitoring function.
[spacer]
CBF_1: Evaluation IN
022 184
0: Without Fig. 3-161, (p. 3-207)
7 Settings P634
P634/EN M/R-42-A // P634311653 7-95