Parameter Address
Default Min Max Unit Logic Diagram
[spacer]
DTOC1: Ineg>>> PSx
076 199 077 199 078 199 079 199
Blocked 0.10 8.00 Inom Fig. 3-110, (p. 3-156)
[spacer]
DTOC2: Ineg>>> PSx
076 209 077 209 078 209 079 209
Blocked 0.10 8.00 Inom
[spacer]
DTOC3: Ineg>>> PSx
076 219 077 219 078 219 079 219
Blocked 0.10 8.00 Inom
[spacer]
DTOC4: Ineg>>> PSx
099 172 099 173 099 174 099 175
Blocked 0.10 8.00 Inom
[spacer]
Setting for the operate value of the Ineg>>> stage.
[spacer]
DTOC1: Ineg> dynamic PSx
076 200 077 200 078 200 079 200
1.00 0.10 8.00 Inom Fig. 3-110, (p. 3-156)
[spacer]
DTOC2: Ineg> dynamic PSx
076 210 077 210 078 210 079 210
1.00 0.10 8.00 Inom
[spacer]
DTOC3: Ineg> dynamic PSx
076 220 077 220 078 220 079 220
1.00 0.10 8.00 Inom
[spacer]
DTOC4: Ineg> dynamic PSx
099 176 099 177 099 178 099 179
1.00 0.10 8.00 Inom
[spacer]
Setting for operate value Ineg> dynamic. (Ineg = negative-sequence current)
This operate value is effective only while the timer stage MAIN: Hold time
dyn.param. is elapsing.
[spacer]
DTOC1: Ineg>> dynamic PSx
076 201 077 201 078 201 079 201
1.00 0.10 8.00 Inom Fig. 3-110, (p. 3-156)
[spacer]
DTOC2: Ineg>> dynamic PSx
076 211 077 211 078 211 079 211
1.00 0.10 8.00 Inom
[spacer]
DTOC3: Ineg>> dynamic PSx
076 221 077 221 078 221 079 221
1.00 0.10 8.00 Inom
[spacer]
DTOC4: Ineg>> dynamic PSx
099 180 099 181 099 182 099 183
1.00 0.10 8.00 Inom
[spacer]
Setting for operate value Ineg>> dynamic. (Ineg = negative-sequence current)
This operate value is effective only while the timer stage MAIN: Hold time
dyn.param. is elapsing.
[spacer]
DTOC1: Ineg>>> dynamic PSx
076 202 077 202 078 202 079 202
1.00 0.10 8.00 Inom
[spacer]
DTOC2: Ineg>>> dynamic PSx
076 212 077 212 078 212 079 212
1.00 0.10 8.00 Inom
[spacer]
DTOC3: Ineg>>> dynamic PSx
076 222 077 222 078 222 079 222
1.00 0.10 8.00 Inom
P634 7 Settings
7-162 P634/EN M/R-42-A // P634‑311‑653