Parameter Address
Default Min Max Unit Logic Diagram
Overload recording
OL_RC: Reset record. USER
100 003
0: don't execute Fig. 3-76, (p. 3-110)
[spacer]
Reset of the overload memory.
Parameter Address
Default Min Max Unit Logic Diagram
Fault recording
FT_RC: Trigger USER
003 041
0: don't execute Fig. 3-82, (p. 3-119)
[spacer]
Fault recording is enabled from the local control panel for 500 ms.
[spacer]
FT_RC: Reset record. USER
003 006
0: don't execute Fig. 3-83, (p. 3-120)
[spacer]
Reset of the following memories:
●
LED indicators
●
Fault memory
●
Fault counter
●
Fault data
●
Recorded fault values
Parameter Address
Default Min Max Unit Logic Diagram
Thermal overload
protection
THRM1: Reset replica USER
039 120
0: don't execute Fig. 3-133, (p. 3-181)
[spacer]
Reset of the thermal replica of the thermal overload protection 1.
Parameter Address
Default Min Max Unit Logic Diagram
Thermal overload
protection
THRM2: Reset replica USER
039 180
0: don't execute
[spacer]
Resetting the thermal replica of the thermal overload protection function.
8 Information and Control Functions P634
P634/EN M/R-42-A // P634‑311‑653 8-157