Page 163
Appendix| EtherCAT
optoNCDT 2300
A 7.3.3.6 Object 2105h: Factory settings
2105 RECORD Factory settings
Subindices
0 VAR Number of entries 3 Unsigned8 ro
1 VAR Factory settings FALSE BOOL rw
2 VAR Keep device settings FALSE BOOL rw
3 VAR Reset material only FALSE BOOL rw
Further details can be found in the section Extras, see Chap. 7.7.2, and Factory settings, see Chap. A 6.3.5.3.
A 7.3.3.7 Object 2131h: Light source
2131 RECORD Light source info
Subindices
0 VAR Number of entries 1 Unsigned8 ro
1 VAR Laser power 2 Unsigned8 rw
Laser power, see Chap. 3.3 Exposure control)
0 - off, 1 - reduced, 2 - 100 % Laser power (1 mW)
A 7.3.3.8 Object 2154h: Measuring program
2154 VAR Measuring program 0 Unsigned8 rw
Further details can be found in the section Measuring program, see Chap. 7.4.1.
0 - Displacement measurement diffuse, 1 - Displacement measurement direct, 2 - Thickness measurement
A 7.3.3.9 Object 2161h: Peak selection at distance measuring
2161 VAR Peak distance measuring selection 0 Unsigned8 rw
Further details can be found in the section Peak Selection displacement Measurement, see Chap. A 6.4.1.2.
0 – Output of peak with highest amplitude (standard for diffuse reflection)
1 – Output of peak with largest area
2 – Output of displacement 1 (complies with backside fading out of diffuse reflection)