5 - 12
5.3 Settings and Procedures before Operation
5
SETTINGS AND PROCEDURES BEFORE OPERATION
(2) When configuring a single CPU system
* 1 To write the parameters, connect the utility to the C Controller module with the write
authority.( Section 5.11, Section 9.1.3)
Figure 5.9 Single CPU system configuration
Figure 5.10 Flowchart for single CPU system configuration
Development environment (PC)
Ethernet
C Controller module
Procedures for operation
Start up the C Controller module.
On the C Controller setting utility, make system setting
necessary to use the C Controller module.
Perform I/O assignment of the main base unit and
extension base unit.
Perform the switch setting and detail setting of each
module.
Write the set parameters from the <<Online operation>>
tab of the C Controller setting utility to the C Controller
module.
Reset the C Controller module with the RESET/SELECT
switch. (Resetting the module makes the written
parameters effective.)
Move the RUN/STOP/MODE switch of the C Controller
module from STOP to RUN, and check that the C
Controller module is in the RUN status (the RUN LED is
lit).
On the C Controller setting utility, check the operation
status (e.g. errors). (Module information, Event history,
Module monitor, system information, etc.)
Is there no error?
Create and debug a user program using Tornado, and
register it to the C Controller module.
Operation
Section 9.2.8 (2), (3)
No
Yes
*1
This section (1)
Section 9.2.7
Section 9.2.8 (1)
Section 9.2.6
Section 5.4 (3)
Section 5.4 (2)
Section 9.2.2, 9.2.3,
9.2.5
Chapter 10
Section 9.2.8 (2), (3)