3-44
3-9 Parameter List
3
Operation
Analog monitor
C027 FM selection
When inverter is in sensor vector control
(A044=05) the real motor speed from the
motor encoder (d008 monitor) is used instead
of the output frequency.
00: Output FQ (Output frequency)
01: Output I (Output current)
02: Output TRQ (Output torque)
03: Pulse FQ (Digital output frequency)
04: Output V (Output voltage)
05: Power
06: Thermal (Thermal load rate)
07: LAD-FQ (LAD frequency)
08: Pulse I (Digital current monitor)
09: Motor tmp (Motor temperature)
10: Heatsink tmp (Fin temperature)
12: YA0 (Drive programming)
19: OP1 (Option board 1)
20: OP2 (Option board 2)
00 No
4-109
4-118
C028 AM selection
When inverter is in sensor vector control
(A044=05) the real motor speed from the
motor encoder (d008 monitor) is used instead
of the output frequency.
00: Output FQ (Output frequency)
01: Output I (Output current)
02: Output TRQ (Output torque)
04: Output V (Output voltage)
05: Power
06: Thermal (Thermal load rate)
07: LAD-FQ (LAD frequency)
08: Pulse I (Digital current monitor)
09: Motor tmp (Motor temperature)
10: Heatsink tmp (Fin temperature)
11: Out TRQ sign (Output torque <signed>)
13: YA1 (Drive programming)
19: OP1 (Option board 1)
20: OP2 (Option board 2)
00 No
4-110
4-118
C029 AMI selection
When inverter is in sensor vector control
(A044=05) the real motor speed from the
motor encoder (d008 monitor) is used instead
of the output frequency.
00: Output FQ (Output frequency)
01: Output I (Output current)
02: Output TRQ (Output torque)
04: Output V (Output voltage)
05: Power
06: Thermal (Thermal load rate)
07: LAD-FQ (LAD frequency)
09: Motor tmp (Motor temperature)
10: Heatsink tmp (Fin temperature)
14: YA2 (Drive programming)
00 No
C030
Digital current
monitor reference
value
0.20 × Rated current to
2.00 × Rated current (Under 55 kW)
0.20 × Rated current to
1.50 × Rated current (Over 75 kW)
Rated
current
Yes A 4-109
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.