4-46
4-2 Function Mode
4
Functions
Input Power Supply Phase Loss Protection Function Selection
•This function outputs an alarm when the Inverter's input power supply has phase loss.
Phase loss may cause the Inverter to fail, as follows:
•The main capacitor ripple current increases, resulting in remarkable reduction in the capacitor's
service life.
•When load is applied, the Inverter's internal converter or thyristor may be damaged.
Electronic Thermal Function
•Causes a trip to protect the motor from overheating. Set this according to the motor rated current.
•Provides the most appropriate protection characteristics, taking into account the decline of the
motor cooling capability at a low speed.
•Outputs an alarm signal before an electronic thermal trip.
•Rated values will be affected by the HD, ND selection.
* To switch to the 2nd/3rd control, allocate 08 (SET)/17 (SET3) to the desired multi-function input and then turn it
on.
*1.
Set a percentage relative to the electronic thermal multiplication value. When the value reaches 100%, an
overload trip (E05) occurs.
Parameter No. Function name Data Default setting Unit
b006
Input phase loss protection
selection
00: OFF (Disabled)
01: ON (Enabled)
01
Parameter No. Function name Data Default setting Unit
b012 Electronic thermal level
0.20 × Rated current to 1.00 ×
Rated current
Rated current Ab212 *2nd electronic thermal level
b312 *3rd electronic thermal level
b013
Electronic thermal
characteristics selection
00: Reduced TRQ (Reduced torque
characteristics)
01: Const TRQ (Constant torque
characteristics)
02: Free set (Free setting)
00 b213
*2nd electronic thermal
characteristics selection
b313
*3rd electronic thermal
characteristics selection
b015
Free setting, electronic thermal
frequency 1
0.00 to 400.00 0.00 Hzb017
Free setting, electronic thermal
frequency 2
b019
Free setting, electronic thermal
frequency 3
b016
Free setting, electronic thermal
current 1
0.0 to Rated current 0.0 Ab018
Free setting, electronic thermal
current 2
b020
Free setting, electronic thermal
current 3
C061 Thermal warning level 0 to 100
*1
80%
Related functions C021 to C025, C026