3-45
3-9 Parameter List
3
Operation
Multi-function output terminal
C031
Multi-function output
terminal 11 contact
selection
00: NO
01: NC
00
No 4-96
C032
Multi-function output
terminal 12 contact
selection
C033
Multi-function output
terminal 13 contact
selection
C034
Multi-function output
terminal 14 contact
selection
C035
Multi-function output
terminal 15 contact
selection
C036
Relay output (AL2,
AL1) contact
selection
00: NO contact at AL2; NC contact at AL1
01: NC contact at AL2; NO contact at AL1
01
Level and output terminal status
C038
Light load signal
output mode
00: ACC/DEC/CST (Enabled during
acceleration/deceleration/constant
speed)
01: Const (Enabled only during constant
speed)
01 No
4-106
C039
Light load detection
level
0.0 to 2.00 × Rated current (0.4 to 55 kW)
0.0 to 1.80 × Rated current (75 to 132 kW)
Rated
current
No A
C040
Overload warning
signal output mode
00: ACC/DEC/CST (Enabled during
acceleration/deceleration/constant
speed)
01: Const (Enabled only during constant
speed)
01 No
4-49
C041
Overload warning
level
0.0: Does not operate.
0.1 × Rated current to 2.00 × Rated current
(0.4 to 55 kW)
0.1 × Rated current to 1.80 × Rated current
(75 to 132 kW)
Rated
current
No A
C042
Arrival frequency
during acceleration
0.00 to 400.00 0.00 No Hz
4-98
C043
Arrival frequency
during deceleration
0.00 to 400.00 0.00 No Hz
C044
PID deviation
excessive level
0.0 to 100.0 3.0 No % 4-31
C045
Arrival frequency
during acceleration 2
0.00 to 400.00 0.00 No Hz
4-98
C046
Arrival frequency
during deceleration 2
0.00 to 400.00 0.00 No Hz
C052
PID FB upper limit
0.0 to 100.0
100.0
No %
4-31
C053
PID FB lower limit
0.0 to 100.0 0.0 No %
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.