4-120
4-2 Function Mode
4
Functions
Stabilization Parameter
•This function adjusts to reduce motor hunting.
•In case of motor hunting, check whether motor capacity H003/H203 and motor pole number
selection H004/H204 match your motor. If they do not, match them. If the motor's primary
resistance is smaller than that of the standard motor, increase the H006/H206/H306 set value
gradually. To run a motor with a capacity larger than the Inverter's rated capacity, reduce the set
value.
•Other than this function, the following methods are suggested to reduce hunting:
Lower the carrier frequency (b083). (Refer to page 4-68.)
Lower the output voltage gain (A045). (Refer to page 4-24.)
Auto Return Initial Display
•Ten minutes after last key operation display returns to the initial parameter set by b038.
Data Read/Write Selection
•Restrict the data read/write operation by 3G3AX-OP05.
Option I/F cmd W Register 1 to 10
•When communication option board is used these parameters are used to define a user exchange
area with the master unit. Refer to especific option board manual for details.
Parameter No. Function name Data Default setting Unit
H006/H206/H306 Stabilization parameter
0 to 255:
If hunting occurs, adjust the set value.
100
A045 Output voltage gain
20 to 100:
If hunting occurs, reduce the set value.
100 %
b083 Carrier frequency
0.5 to 15.0:
If hunting occurs, reduce the set value.
5.0 kHz
Parameter No. Function name Data Default setting
b164 Auto return initial display
00: OFF (Disabled)
01: ON (Enabled)
00
Parameter No. Function name Data Default setting
b166 Data read/write selection
00: R/W OK (Read/Write OK)
01: R/W Protected (Read/Write protected)
00
Parameter No. Function name Data Default setting
P160 to P169
Option I/F cmd W register
1 to 10
0000 to FFFF 0000