4-100
4-2 Function Mode
4
Functions
Overtorque (OTQ)
This function outputs a signal when detecting a motor output torque estimated value exceeding a
specified level.
Enabled when "overtorque signal" is selected in the multi-function output selection. You can use
this function only when "sensorless vector control", "0-Hz sensorless vector control", or "sensor
vector control" is selected in V/f characteristics selection A044/A244. With other settings, the
output is unstable.
For elevating machines, use this signal for releasing the brake. To close the brake, use the
frequency arrival signal.
Parameter No. Function name Data Default setting Unit
C021 to C025
Multi-function output
terminal 11 to 15 selection
07: OTQ (Overtorque)
-
C026
Relay output (AL2, AL1)
function selection
05
C055
Overtorque level
(Forward power running)
0 to 200 (0.4 to 55 kW)
0 to 180 (75 to 132 kW)
OTQ signal output level for forward
power running
200 (Under 55 kW)
180 (Over 75 kW)
%
C056
Overtorque level
(Reverse regeneration)
0 to 200 (0.4 to 55 kW)
0 to 180 (75 to 132 kW)
OTQ signal output level for reverse
regeneration
200 (Under 55 kW)
180 (Over 75 kW)
%
C057
Overtorque level
(Reverse power running)
0 to 200 (0.4 to 55 kW)
0 to 180 (75 to 132 kW)
OTQ signal output level for reverse
power running
200 (Under 55 kW)
180 (Over 75 kW)
%
C058
Overtorque level
(Forward regeneration)
0 to 200 (0.4 to 55 kW)
0 to 180 (75 to 132 kW)
OTQ signal output level for forward
regeneration
200 (Under 55 kW)
180 (Over 75 kW)
%
Related functions A044, A244, A344, C063