4-184
4-4 Communication Function
4
Functions
<Holding Register Number List (Monitor)>
Register
No.
Function name
Function
code
R/W Monitor and setting parameters
Rresolution
1001h
Output frequency monitor
d001
(HIGH)
R 0.00 to 400.00 0.01 [Hz]
1002h
d001
(LOW)
1003h Output current monitor d002 R 0.0 to 9999.0 0.1 [A]
1004h Rotation direction monitor d003 R
FWD: Forward
STOP: Stop
REV: Reverse
1005h
PID feedback value monitor
d004
(HIGH)
R 0.00 to 999000.00
1006h
d004
(LOW)
1007h Multi-function input monitor d005 R
2^0: Terminal 1 to 2^7: Terminal 8
2^8: Terminal FW
1008h
Multi-function output
monitor
d006 R
2^0: Terminal 11 to 2^4: Terminal 15
2^6: Relay terminal
1009h
Output frequency monitor
(after conversion)
d007
(HIGH)
R 0.00 to 39960.00 0.01
100Ah
d007
(LOW)
100Bh
Real frequency monitor
d008
(HIGH)
R
-400.00 to 400.00 0.01 [Hz]
100Ch
d008
(LOW)
R
100Dh Torque reference monitor d009 R -200 to 200 1 [%]
100Eh Torque bias monitor d010 R -200 to 200 1 [%]
100Fh Not used
1010h Output torque monitor d012 R -200 to 200 1 [%]
1011h Output voltage monitor d013 R 0.0 to 600.0 0.1 [V]
1012h Input power monitor d014 R 0.0 to 999.9 [kW]
1013h
Integrated power monitor
d015
(HIGH)
R 0.0 to 999999.9 0.1 [h]
1014h
d015
(LOW)
1015h
Total RUN time
d016
(HIGH)
R 0 to 999999 1 [h]
1016h
d016
(LOW)
1017h
Power ON time monitor
d017
(HIGH)
R 0 to 999999 1 [h]
1018h
d017
(LOW)
1019h Fin temperature monitor d018 R -020. to 200.0 0.1 [
C]
101Ah Motor temperature monitor d019 R -020. to 200.0 0.1 [
C]
101Bh
Not used
101Ch
101Dh Life assessment monitor d022 R
2^0: Capacitor on the main circuit board
2^1: Cooling fan rotation speed
reduced