3-46
3-9 Parameter List
3
Operation
Level and output terminal status
C055
Overtorque level
(Forward power
running)
0 to 200 (0.4 to 55 kW) 200
No %
4-100
0 to 180 (75 to 132 kW) 180
C056
Overtorque level
(Reverse
regeneration)
0 to 200 (0.4 to 55 kW) 200
No %
0 to 180 (75 to 132 kW) 180
C057
Overtorque level
(Reverse power
running)
0 to 200 (0.4 to 55 kW) 200
No %
0 to 180 (75 to 132 kW) 180
C058
Overtorque level
(Forward
regeneration)
0 to 200 (0.4 to 55 kW) 200
No %
0 to 180 (75 to 132 kW) 180
C061
Thermal warning
level
0 to 100 80No %4-46
C062 Alarm code selection
00: OFF (Disabled)
01: 3-bit
02: 4-bit
00 No 4-101
C063 0 Hz detection level 0.00 to 100.00 0.00 No Hz 4-101
C064
Fin overheat warning
level
0 to 200 120 No C 4-105
Communication function
C071
Communication
speed selection
(Baud rate selection)
02: Loop-back test
03: 2400 bps
04: 4800 bps
05: 9600 bps
06: 19200 bps
05 No
4-146
C072
Communication
station No. selection
1 to 247 1 No
C073
Communication bit
length selection
7: 7-bit
8: 8-bit
8 No
C074
Communication
parity selection
00: No parity
01: Even
02: Odd
00 No
C075
Communication stop
bit selection
1: 1-bit
2: 2-bit
1No
C076
Communication error
selection
00: Trip
01: Decel-Trip (Trip after deceleration stop)
02: Ignore
03: Free-RUN (Free-run stop)
04: Decel-Stop (Deceleration stop)
02 No
C077
Communication error
timeout
0.00 to 99.99 0.00 No s
4-104
4-146
C078
Communication wait
time
0 to 1000 0 No ms
4-146
C079
Communication
method selection
00: ASCII
01: ModBus-RTU
01 No
Parameter
No.
Function name Monitor or data range
Default
setting
Changes
during
operation
Unit Page
* 2nd/3rd control is displayed when "SET(08)/SET3(17)" is allocated to one of multi-function inputs from C001
to C008.