4-121
4-2 Function Mode
4
Functions
Option I/F cmd R Register 1 to 10
•When communication option board is used these parameters are used to define a user exchange
area with the master unit. Refer to especific option board manual for details.
Profibus Communications
•Use these parameters to define the node address and communication type when 3G3AX-RX-PRT
Profibus unit is used.
CompoNet Communications
•Use these parameters to configure CompoNet network when 3G3AX-RX-CRT CompoNet unit is
used.
Parameter No. Function name Data Default setting
P170 to P179
Option I/F cmd R register
1 to 10
0000 to FFFF 0000
Parameter No. Function name Data Default setting
P180 Profibus node address 0 to 125 -
P181 Profibus clear mode
00: Clear
01: Last value
00
P182 Profibus map selection
00: PPO
01: Conventional
02: Flexible mode
00
Parameter No. Function name Data Default setting
P045
Operation setting at
communications error
00: Trip
01: Decel-Trip (Trip after deceleration stop)
02: Ignore
03: Free run
04: Decel-Stop (Deceleration stop)
00
P046 Instance Number
0: Basic speed I/O
1: Extended speed I/O
2: Extended speed and Torque control
3: Special I/O
4: Extended control I/O
5: Extended control I/O and multifunction
I/O monitor
6: Flexible format
7: Extended speed and Acceleration control
8-20: Not used
1
P048
Operation setting at idle
mode detection
00: Trip
01: Decel-Trip (Trip after deceleration stop)
02: Ignore
03: Free RUN
04: Decel-Stop (Deceleration stop)
00
P190 CompoNet node address 0 to 63 0